Danfoss ECL Comfort 210 Operating Manual page 110

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A232 / A332
MENU > Settings > Optional function
Add. function (Additional function, Relay 5 (X5))
Functionalities related to Relay 5 (X5), sub-types A332.1, A332.2, A332.3
and A332.4 only.
The selected code (3, 4, 5 or 6) determines the functionality:
3: Relay 5 (X5) follows Schedule 1, present in heating circuit.
4: Relay 5 (X5) follows Schedule 2, present in cooling circuit.
5: Relay 5 (X5) follows Schedule, present in "Common controller settings".
6: Relay 5 (X5) goes ON at cooling demand.
See Appendix "Parameter ID overview"
Code: Set the desired functionality
MENU > Settings > Optional function
Acc. output func. (Accessory output function, Relay 4
(X4))
Functionalities related to Relay 4 (X4).
The selected code (0, 1, 2, 3, 4, 5 or 6) determines the functionality:
0: Relay 4 (X4) acts as humidistat in cooling mode only.
1: Relay 4 (X4) acts always as humidistat.
2: Relay 4 (X4) switches according to outdoor temperature. See *Stop at
T out, ID 1x038.
3: Relay 4 (X4) follows Schedule 1, present in heating circuit.
4: Relay 4 (X4) follows Schedule 2, present in cooling circuit.
5: Relay 4 (X4) follows Schedule, present in "Common controller settings".
6: Relay 5 (X4) goes ON at cooling demand.
See Appendix "Parameter ID overview"
Code: Set the desired functionality
110 | © Danfoss | 2017.08
1x083
1x089
The subtype A232.1 contains the codes 0, 1, 2, 3, 4, 5 and 6.
The subtypes A332.1 . . . A332.4 contain the codes 0, 1 and 2.
VI.JM.G2.02