Operating Guide ECL Comfort 210/296/310, application A232 / A332
MENU > Settings > Optional function
Humidistat, diff. (Humidistat, difference for switching)
The activation of the humidistat is determined by the switching difference.
The switching difference is the value between activation and deactivation of
Relay 4 (X4).
Precondition:
The parameter 'Acc. output func. ' (Accessories, output function, ID 11089)
must be set to "0" or "1".
See Appendix "Parameter ID overview"
Value: Set the switching difference
MENU > Settings > Optional function
Humidistat, post t. (Humidistat, post ON-time)
Setting the time where Relay 4 (X4) should remain ON after the humidity
value has fallen below the setpoint 'Humidity, setp' (ID 1x160).
Precondition:
The parameter 'Acc. output func. ' (Accessories, output function, ID 11089)
must be set to "0" or "1".
See Appendix "Parameter ID overview"
Value: Set the post ON-time
VI.JM.G2.02
Humidistat, functionality:
1x158
=
X
Time
=
Y
Humidity
# 1 # =
Humidity (measured by ECA 31)
# 2 # =
'Humidistat, diff.' (ID 1x158)
# 3 # =
'Humidistat, setp.' (ID 1x160)
# 4 # =
Status of Relay 4 (X4)
# 5 # =
'Humidistat, post t.' (ID 1x159)
1x159
© Danfoss | 2017.08 | 111