Outdoor Unit - RK(X)S20-35G2V1B, ARXS20-35G2V1B
Step
4
Disconnect the
connector for the fan
motor [S70].
Release the fan motor
5
lead wire from the hook.
6
Open the hooks and
release the fan motor
lead wire.
7
Remove the 4 screws
and remove the fan
motor.
189
Procedure
[S70]
Fan motor
lead wire
Fan motor
Points
(R9332)
(R7200)
When reassembling, put the
fan motor lead wire through
the back of the fan motor (so
as not to be entangled with
the outdoor fan).
Lead wire
(R7201)
Be sure to remove the lower
screws first. If the upper
screws are removed first, the
fan motor, the center of
gravity of which is toward the
front, may tilt down or fall,
getting you injured.
(R7202)
Removal Procedure
SiBE04-808_B
Outdoor fan
(R3249)