Daikin G-Series Service Manual page 146

Inverter pair wall mounted type
Hide thumbs Also See for G-Series:
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.07
Refer to P.149
Check No.09
Refer to P.150
RK(X)S20-35G2V1B, ARXS20-35G2V1B
RK(X)S20-35G2V1B9, ARXS20-35G3V1B
RK(X)S42G2V1B, ARXS42G2V1B
RK(X)S50G2V1B, ARXS50G2V1B
135
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power and turn it on
again.
Error again or outdoor
fan activated?
NO
Check No. 09
Check the outdoor fan or
related.
OK
Radiation fin dirty?
Slightly dirty
Check No. 07
Check the installation condition.
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above C ˚C and stops when it
drops below D ˚C.
YES
Check the radiation fin
temperature.
Above A
˚C?
YES
NG
Too dirty
A (°C)
80
98
80
95
SiBE04-808_B
WARNING
NO
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors and
fan motor lead wire.
Replace the outdoor unit
PCB.
Clean up the radiation fin.
(R12000)
B (°C)
C (°C)
70
80
75
83
70
75
80
85
Service Diagnosis