External Wiring
Wiring, and noise countermeasures in particular, are based on experience, and it is necessary to
closely manage wiring based on experience and information in the manuals.
 Wiring Routes
Each of the following combinations includes different signal types, properties, or levels. They will
cause the signal-to-noise ratio to drop due to factors such as electrical induction. As a general rule
when wiring, either use separate cables or separate wiring routes for these items. Future mainte-
nance operations and changes to the system will also be made easier by carefully organizing the
wiring from the start.
• Power lines and signal lines
• Input signals and output signals
• Analog signals and digital signals
• High-level signals and low-level signals
• Communications lines and power lines
• DC signals and AC signals
• High-frequency devices (such as Inverters) and signal lines (communications)
 (Routing of) Wiring
Observe the following points when wiring power supply and signal cables.
• When routing signal cables with differing characteristics through the same duct, always keep
them separated.
• As much as possible, avoid routing multiple power supply lines through the same duct. If it can-
not be avoided, then construct a partition between them in the duct and ground the partition.
Signal
cables
(group A)
Signal cables
Power supply cables
Partitioning Methods for Signal and Power Supply Cables
• To avoid overheating the conduits when using conduits for wiring, do not place wires for a single
circuit in separate conduits.
NY-series Industrial Monitor User's Manual (W554)
Signal
Signal
cables
cables
(group B)
(group C)
Signal cables
(a)
(c)
Partition
a
(b)
Signal cables
Power supply cables
(d)