Omron NYM15W-C100 User Manual page 101

Industrial monitor ny-series
Hide thumbs Also See for NYM15W-C100:
Table of Contents

Advertisement

Star Earthing
If the earthing method used for the building is not equipotential bonding or the earthing system is un-
known, choose (a) from among the earthing methods given below.
(a) Connecting devices and noise sources to separate earth electrodes
This is an earthing method to separately ground an earth electrode of the device that is connected
with a communications cable or other devices and an earth electrode of a high-power device that
could be a noise source, such as a motor or inverter.
Each earth electrode must be ground to 100 Ω or less.
Connect the ground lines of the device that is connected with a communications cable and other
devices as a bundle to a single earth electrode. Be sure that the earth electrode is separated by a
minimum of 10 m from any other earth electrode of a device that could be a noise source.
Control panel
NY-series
Industrial Panel PC
(b) Connecting devices and noise sources to a common earth electrode
This is an earthing method to connect the device that is connected with a communications cable,
other devices, and a device that could be a noise source, to a common earth electrode.
This earthing method is not recommended because the device that could be a noise source may
interfere electromagnetically with other devices.
Control panel
NY-series
Industrial Panel PC
NY-series Industrial Monitor User's Manual (W554)
NY-series
Industrial Box PC
Other device
Hub
10 m min.
NY-series
Industrial Box PC
Other device
Hub
5 Installation
NY-series
A device that could be
a noise source
Industrial Monitor
A device that could be
NY-series
Industrial Monitor
a noise source
5
5 - 21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nym15w-c106Nym12w-c100Nym12w-c106

Table of Contents