5 Installation
5-2-3
Temperature
The temperature inside a control panel may be at least 10 to 15°C higher than outside the panel. Im-
plement the following measures against overheating at the installation site and in the control panel,
and allow a sufficient margin for the temperature.
Distance for Cooling
Adequate airflow around the Industrial Monitor is required.
Additional Information
• The ambient temperature must be within the operating range.
Refer to 4-4 Environmental Specifications on page 4 - 12 for temperature specifications.
• Allow space to accommodate for the bending radius of the cables.
Refer to:
• 2-4-1 DVI Cables on page 2 - 10
• 2-4-2 USB Type-A to USB Type-B Cables on page 2 - 11
• 2-4-3 NY Monitor Link Cables on page 2 - 12
for cable bending requirements.
Provide enough space for good air flow and ensure the following minimum distances are observed
around the sides of the Industrial Monitor for landscape
X
Item
X
50 mm
Y
100 mm
Z
50 mm
*1.
Measure the minimum distances X and Y at the air openings in the sides of the Industrial Monitor.
5 - 6
A
Y
X
Y
A
and portrait
B
Y
X
X
Y
*1
Minimum Distance
NY-series Industrial Monitor User's Manual (W554)
B
orientations.
A
+
B
Z