System Configuration and Functions
Override End Conditions
When either of the following conditions is satisfied, the function is released.
•When 60 seconds has elapsed under the override state
•All muting sensors are turned OFF
•When the reset input is turns from OFF to ON and/or the test input turns from ON to OFF
Override state can be released if a sensor transitions to lockout as well.
Muting input 1
Muting input 2
Reset input
Test input
Override state
Muting lamp
(External indicator)
F3SJ Unblocked
/Blocked
Safety output
*1 Order of reset input ON -> OFF and test input OFF -> ON can be arbitrary for override start conditions.
(Switching time difference must be within 0.3s)
*2 There are 3 override end conditions. For details, see override end conditions.
- T1: Override Input Time Limit
Maximum value of input time difference between reset input ON -> OFF and test input OFF -> ON It is set as 0.3s.
- T2: Override Time Limit
Continuance time is set at 60s in the overriding condition. If override state exceeds this time, the function is canceled.
Operation of the F3SJ's Internal Indicators When Override Function Is Performed
•Muting input 1 indicator turns ON when an input is applied to muting input 1.
•Muting input 2 indicator turns ON when an input is applied to muting input 2.
•Muting input 1 and 2 indicators blink while muting overriding
•Muting error indicator turns ON when a muting error occurs.
F3SJ-A
42
User's Manual
ON
OFF
ON
OFF
ON
OFF
ON
OFF
0.1s max.
Enabled
Disabled
blinking
OFF
Unblocked
Blocked
ON
OFF
*1
T1 (0.3s max.)
T2 max.
*2