Omron F3SJ-A series User Manual page 56

Safety light curtain
Hide thumbs Also See for F3SJ-A series:
Table of Contents

Advertisement

System Configuration and Functions
Timing Chart
Muting sensor A1
Muting sensor B1
Muting sensor A2
Muting sensor B2
Muting state
Muting lamp
(External indicator)
F3SJ Unblocked
/Blocked
Safety output
*1 The value is applied to a single sensor. Values for connected sensors are:
# of connections
Single
2 connected
3 connected
•T1min: Muting input time limit (minimum value)
This is set to 0.03 sec., the minimum value for the input time difference between muting input 1 and 2.
A muting error occurs when the input time difference between muting input 1 and 2 is less than this
value.
•T1max: Muting input time limit (maximum value)
This is set to 3 sec., the maximum value for the input time difference between muting input 1 and 2.
•T2: Muting time limit
This is set to 60 sec., the muting function continuation time. When this muting state exceeds this time,
muting is released.
•T3: Muting input time with allowable waveform cracks
This is the maximum value for the waveform cracks allowed for muting input 1 and 2 when muting is
in effect. It is set to 0.1 sec.
F3SJ-A
38
User's Manual
T3(0.1s ) max.
ON
OFF
T1min to T1max
ON
OFF
ON
OFF
ON
OFF
0.15s max. *1
Enabled
Disabled
Blinking
OFF
Unblocked
Blocked
ON
OFF
*1 Value (s)
0.15
0.26
0.29
T3(0.1s ) max.
T3(0.1s ) max.
T3(0.1s ) max.
T2 max.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents