Installation Example 2 of Standard Muting Mode (using 4
muting sensors)
This installation example uses 4 through-beam type photoelectric sensors as muting sensors.
The use of 4 muting sensors is useful when the length of the workpieces (L) is constant or longer.
1.
Before a workpiece passes through
Workpiece
L
d2: Maximum distance required for the muting sensor to keep the muting function enabled
D2, D3: Minimum distances required for the muting sensor to keep the muting function enabled
All muting sensors are turned OFF and the safety function of the F3SJ is working.
2.
The muting sensors are blocked and the safety function of the F3SJ is disabled
When muting sensors A1 and B1 are turned ON in this order, the muting function is enabled. In this
state, the safety function of F3SJ is disabled.
Hazardous zone
A1
F3SJ
B2
V
B1
A2
d2
D2
D3
Hazardous zone
A1
F3SJ
B2
Workpiece
B1
A2