Toshiba TOSVERT VF-PS1 Instruction Manual page 99

Variable torque inverter
Hide thumbs Also See for TOSVERT VF-PS1:
Table of Contents

Advertisement

[Example: Procedure of calibrating the meter connected to the terminal AM to which "output current" is assigned.]
Key operated
LED display
MODE


ENT

ENT

ENT


ENT

ENT

ENT
MODE
[Procedure of calibrating the output for signed data from 0-10V using FM terminal.]
(Adjustment level: 5V output at 0Hz, 9V output at forward running in FH, 1V output at reverse running in FH)
FM output voltage
(V)
9
5

1
FH
0
(Reverse run)
Displays the operation frequency. (Perform during operation stopped.)

(When standard monitor display selection  =  [Output frequency])
The first basic parameter "History function (  )" is displayed.
Press either the
Pressing the ENTER key allows the reading of parameter setting.

Set the parameter at  (fixed output for meter calibration 2) by pressing

the
key.
Press the ENTER key to save the change. Then,  and the set
value are displayed alternately.

Select the AM terminal meter adjustment  by pressing the △ key.

Press the ENTER key to switch to the data display mode.
Press either the
Adjust the pointer to the graduation to which you want it to point when the
inverter passes a current 100% larger than its rated output current.
(The meter reading will change at this time but be careful because there
will be no change in the inverter's indication).
By setup, before the needle of meter beings to sway, it will take time.
Press the ENTER key to save the change. Then  and the set value are
displayed alternately.
Select the "AM terminal meter adjustment  " by pressing the

Pressing the ENTER key allows the reading of parameter setting.

Return the parameter setting to  (output current display).
Press the ENTER key to save the change. Then,  and the set
value are displayed alternately. 
Press the MODE key three times to return to the running frequency
display mode. (When standard monitor display selection  = 

[Output frequency])
1) Select the switch of SW2 (for FM) to 0-10V side.
2) Set the parameter  =  (Signed output
3) Set the FM output voltage becomes 5V at 0Hz with

4) Set the parameter  =  (Signed fixed output 1).
5) Set the FM output voltage becomes 9V with adjusted the
6) Set the parameter  =  .
FH
7) Finish
(Forward run)
E-29
Operation
or
key to select "  . "
key or the
key to adjust the meter.
[Hint]
It's easier to make the
adjustment if you push and
hold for several seconds.
frequency).
adjusted the parameter  .
parameter  .
E6581386
5
key.