Parameter setting
Positive
Negative
logic
logic
Low current detection


Over-torque detection


Braking resistor


overload pre-alarm
In emergency stop


In retry


PID deviation limit


Run/Stop


Serious failure (OCA,


OCL, EF, phase failure,
etc.)
Light failure (OL, OC1, 2,


3, OP)
Commercial


power/inverter switching
output 1
Commercial
power/inverter switching


output 2
Cooling fan ON / OFF


In jogging operation (In


jog run)
Operation


panel/terminal board
operation switching
Cumulative operation


time alarm
PROFIBUS/DeviceNet/CC-Li


nk communication error
Forward/reverse


switching
Ready for operation 1


Ready for operation 2


In (pre-)alarm status


Inverter healthy output


RS485 communication


error


Error code output 1


Error code output 2


Error code output 3


Error code output 4


Error code output 5
Error code output 6


Specified data output 1


Specified data output 2


Function
Operation output specifications (in case of positive logic)
ON: The state that inverter output current is  set value
or larger continued more than  set value.
ON:The state that torque component is  ,  set
value or larger continued more than  set value.
ON:A certain rate of braking resister overload trip (  )
detection time is over.
OFF:The detection time is within a certain limit.
ON:In emergency stop operation (  is indicated).
OFF:The detection time is within a certain limit.
ON:In retry operation (  is indicated).
OFF:No retry operation is performed.
ON:PID deviation is in  or  set value.
ON:Running frequency is output or DC injection breaking
(  ) is performed.
ON:Serious failure (  ,  ,  , phase failure,
abnormal output, short-circuit) is detected.
OFF:Inverter has recovered from serious failure. (Serious
failure has been reset)
ON:Light failure (  ,  ,  ,  ,  ) is detected.
OFF:Inverter has recovered from light failure. (Light failure has
been reset)
Refer to Section 6.17.
Refer to Section 6.17.
ON:Cooling fan is in operation.
OFF:Cooling fan is off operation.
ON:In jog run
OFF:In normal operation
ON:In operation by terminal board.
OFF:In operation by operation panel.
ON:Cumulative operation time is beyond the  set
value.
OFF:Cumulative operation time is less than the  set
value.
ON:Communication error occurred.
OFF:Communication error is canceled (reset).
OFF:In forward operation.
ON:In reverse operation.
It output command status while operation is stopped.
(When command status is not active, It will be "OFF")
ON:In operable status (exclude during deceleration stop) or
operation can be started with frequency command input as an
operation switching answer-back.
OFF:In inoperable status.
ON:In operable status or operation can be started with RUN
signal and frequency command input.
OFF:In inoperable status.
ON:More than one of alarm, pre-alarm, undervoltage, low
current over-torque, poor control power supply, PID deviation
limit, abnormal frequency setting or torque limit have occurred
or detected.
OFF:All the alarms above are canceled.
ON and OFF are alternately output at intervals of 1 second.
ON:Communication error occurred.
OFF:Communication error is canceled (reset).
Output the error code in 6-bit.
Output of the designated data in 7-bit.
G-7