Three-Phase 400 V Class Drive Models 4O0011 To 4O0077 - YASKAWA U1000 Technical Manual

Matrix drive low harmonic regenerative drive for industrial applications 200 v class: 7.5 to 75 kw (10 to 100 hp nd) 400 v class: 5.5 to 580 kw (7.5 to 775 hp nd)
Hide thumbs Also See for U1000:
Table of Contents

Advertisement

u

Three-Phase 400 V Class Drive Models 4o0011 to 4o0077

Item
Drive Model
Maximum Applicable Motor
<1>
Capacity kW (HP)
Rated Input
<2>
Current (A)
Rated Input
<3>
Capacity (kVA)
Rated Output
Input/
<4> <5>
Current (A)
Output
Rating
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Rated Voltage
Rated Frequency
Allowable Voltage Fluctuation
Power
Supply
Allowable Frequency Fluctuation
Allowable Phase Power Supply
Voltage Unbalance
Harmonic Current Distortion
Input Power Factor
<1> The motor capacity (HP) refers to an NEC 4-pole motor. The rated output current of the drive should be equal to or greater than the motor current.
Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated input capacity is calculated with a power line voltage of 480 V × 1.1.
<4> The rated output current of the drive should be equal to or greater than the motor rated current.
<5> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.
<6> Commercial power mode results in near zero input harmonics. Existing power conditions and operation mode can affect input harmonics.
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Table A.4 Power Ratings (Three-Phase 400 V Class)
4o0011 4o0014 4o0021 4o0027 4o0034 4o0040 4o0052 4o0065 4o0077
HD Rating
3.7 (5)
5.5 (7.5)
ND Rating
5.5 (7.5) 7.5 (10)
HD Rating
8.7
10
ND Rating
10
13
HD Rating
8
9
ND Rating
9
12
HD Rating
9.6
11
ND Rating
11
14
(Derating may be required for applications that start and stop frequently)
4 kHz (User adjustable up to 10 kHz. Derating may be required.)
Three-phase 4Aoooo and 4Poooo 380 to 500 Vac 50/60 Hz
Three-phase 4Eoooo and 4Woooo 380 to 480 Vac 50/60 Hz
<6>
Specification
7.5 (10)
11 (15)
15 (20) 18.5 (25) 22 (30)
11 (15)
15 (20) 18.5 (25) 22 (30)
13
19
25
19
25
31
12
17
22
17
22
28
14
21
27
21
27
34
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
Proportional to input voltage
400 Hz (User-adjustable)
-15 to 10%
±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
2% or less
5% or less (IEEE519 compliant)
0.98 or more (During rated operation)
A.2 Power Ratings
30 (40)
37 (50)
30 (40)
37 (50)
45 (60)
31
36
47
36
47
59
28
33
43
33
43
54
34
40
52
40
52
65
<6>
59
70
54
64
65
77
A
479