4.3 The Drive and Programming Modes
u

Simplified Setup Using the Setup Group

The Setup Group lists the basic parameters necessary to set up the drive for an application. This group expedites the startup
process for an application by showing only the most important parameters for the application.
n
Using the Setup Group
Figure 4.7
illustrates how to enter and how to change parameters in the Setup Group.
The first display shown when entering the Setup Group is the Application Selection menu. Skipping this display will keep the
current Setup Group parameter selection. The default setting for the Setup Group is a group of parameters most commonly
use in general-purpose applications. Pressing the ENTER key from the Application Selection menu and selecting an
Application Preset will change the Setup Group to parameters optimal for the application selected.
Selection on page
154.
In this example, the Setup Group is accessed to change b1-01 from 1 to 0. This changes the source of the frequency reference
from the control circuit terminals to the digital operator.
- MODE -
DRV
Rdy
FREF (AI)
U1-01= 0.00Hz
U1-02= 0.00Hz
RSEQ
U1-03= 0.00A
RREF
JOG
FWD
Press until
Frequency reference
Setup Group
appears when
powered up
<1> Use the up and down arrow keys to scroll through the Setup Group. Press the ENTER key to view or change parameter settings.
<2> To return to the previous menu without saving changes, press the ESC key.
144
- MODE -
PRG
Quick Setting
HELP
FWD
DATA
appears
Figure 4.7 Setup Group Example
<1>
- SETUP -
PRG
Application Sel
A1-06= 0
*0*
General
Home
FWD
DATA
Parameter Display
- SETUP -
PRG
Control Method
A1-02= 2
*2*
Open Loop Vector
Home
FWD
DATA
- SETUP -
PRG
Ref Source 1
b1-01= 1
*1*
Analog Input
Home
FWD
DATA
- SETUP -
PRG
Run Source 1
b1-02= 1
*1*
Digital Inputs
Home
FWD
DATA
- SETUP -
PRG
StallP Decel Sel
L3-04= 1
*1*
General Purpose
Home
FWD
DATA
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Refer to Application
- SETUP -
PRG
Ref Source 1
b1-01=
1
*1*
Analog Input
"1"
FWD
Control Circuit
Terminal
<2>
Entry Accepted
- SETUP -
PRG
Ref Source 1
b1-01=
0
*1*
Operator
"1"
FWD
Operator
<2>