4.6 Application Selection
u

Setting 4: HVAC Fan Application

No.
A1-02
Control Method Selection
b1-04
Reverse Operation Selection
b1-17
Run Command at Power Up
C6-01
Drive Duty Mode Selection
C6-02
Carrier Frequency Selection
H2-03
Terminal P2-PC Function Selection
L2-01
Momentary Power Loss Operation Selection
L8-03
Overheat Pre-Alarm Operation Selection
L8-38
Carrier Frequency Reduction Selection
No.
b1-01
Frequency Reference Selection 1
b1-02
Run Command Selection 1
b1-03
Stopping Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-02
Carrier Frequency Selection
d2-01
Frequency Reference Upper Limit
u

Setting 5: Air Compressor Application

No.
A1-02
Control Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Drive Duty Mode Selection
E1-03
V/f Pattern Selection
L2-01
Momentary Power Loss Operation Selection
No.
b1-01
Frequency Reference Selection 1
b1-02
Run Command Selection 1
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
156
Table 4.11 HVAC Fan: Parameter Settings
Parameter Name
Table 4.12 HVAC Fan: User Parameters (A2-01 to A2-16)
Parameter Name
Table 4.13 Air Compressor: Parameter Settings
Parameter Name
Table 4.14 Air Compressor: User Parameters (A2-01 to A2-16):
Parameter Name
0: V/f Control
1: Reverse Prohibited
1: Run command issued, motor operation start
1: Normal Duty (ND)
3: 4.0 kHz
39: Watt Hour Pulse Output
2: CPU Power Active - Drive will restart if power returns prior
to control power supply shut down.
4: Operation at lower speed
2: Enabled across entire frequency range.
No.
d2-02
Frequency Reference Lower Limit
E1-03
V/f Pattern Selection
E1-04
Maximum Output Frequency
E2-01
Motor Rated Current
H3-11
Terminal A2 Gain Setting
H3-12
Terminal A2 Setting Bias
L2-01
Momentary Power Loss Operation Selection
o4-12
kWh Monitor Initialization
0: V/f Control
1: Reverse Prohibited
5.0 s
5.0 s
0: Heavy Duty (HD)
F: Custom V/f Pattern
1: Enabled
No.
E1-03
V/f Pattern Selection
E1-07
Middle Output Frequency
E1-08
Middle Output Frequency Voltage
E2-01
Motor Rated Current
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Default Setting
Parameter Name
Default Setting
Parameter Name