Address Assignment and Installation

3.3 Installing

Rules for Address Assignment
Warning
Observe the following rules when assigning the address:
*: A network consists of one or more subnets. "Network-wide" means across subnet
boundaries.
**: "Station-wide" means a station in
I-slave)
3.3
Installing
3.3
Installing Fail-Safe Modules
Fail-safe power modules, electronic modules, and terminal modules are part of the ET 200S
range of modules. They are installed using the same procedure as for all standard modules
in an ET 200S.
For more information about module installation, consult the
manual.
Mounting Dimensions
Note that fail-safe modules are 30 mm wide (twice as wide as standard ET 200S modules).
Otherwise, information provided in the
3-4
Make sure that the address switch setting on the module matches the PROFIsafe address in
STEP 7 HW Config
.
The switch setting on the address switch of the F-I/O, in other words, its PROFIsafe destination
address must be unique within the network* and station** (throughout the system). A maximum of
1,022 PROFIsafe destination addresses can be assigned in one system. That is, a maximum of
1,022 F-modules can be addressed using PROFIsafe.
Exception: In different I-slaves, F-I/O can have the same PROFIsafe target addresses since they
are only addresses within the station, in other words by the F-CPU in the I-slave.
The following restriction applies only to ET 200S F-submodules whose default PROFIsafe
addresses cannot be modified in
If you use ET 200S F-modules whose PROFIsafe addresses cannot be modified in
PROFIBUS network, you can only operate one DP master/IO controller with F-CPU in this network;
otherwise, the system-wide uniqueness of the PROFIsafe addresses cannot be guaranteed.
HW Config
:
HW Config
(for example an S7-300 station or an
ET 200S Distributed I/O System
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
HW Config
ET 200S Distributed I/O System