Siemens SIMATIC ET 200S Installation And Operating Manual page 25

Distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Power Modules: Maximum Configuration per Voltage Group
Table 2-5
Power Modules
PM-E F pm DC24V
PROFIsafe
PM-E F pp DC24V
PROFIsafe
PM-D F DC24V
PROFIsafe
* Reason:
Switching time (up to 200 ms)
Duration (to 200 ms)
ET 200S: Limitations and maximum configuration
You will find information on the limitations and maximum configuration of the standard
ET 200S in the
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
2.3 Maximum Number of Connectable Modules/Maximum Configuration
Maximum Configuration per Voltage Group
Maximum Current
Carrying Capacity
10 A
10 A briefly*
5 A permanent*
0.15 A
0.15 A
ET 200S Distributed I/O System
Connectable Modules/Motor Starters
The number of modules that can be connected
depends on the total current of all modules in the
voltage group. The total combined current cannot
exceed 10 A. The total current is determined by
the digital output modules.
The number of connectable motor starters/
modules depends on the total current of all motor
starters/modules of this voltage group. The total
combined current cannot exceed 10 A.
Current consumption of the F-motor starters
U1 (electronics supply)
manual.
Configuring
SG (shutdown groups)
0.25 A
0.06 A
2-7