Parameters of the PM-E F pm DC24V PROFIsafe

STEP 7
Parameters in
The following table presents the parameters that can be assigned for the
PM-E F pm 24 VDC PROFIsafe.
Table 7-4
Parameter
F-Parameters:
F_destination_address 1 to 1022
F monitoring time
Module Parameters:
Behavior after channel
faults*
Channel fault
Readback Time
Diagnostics: Wire
break
DO channel 1
Readback Time
Diagnostics: Wire
break
* This setting is only relevant when S7 Distributed Safety V5.4 or higher is installed.
Readback Time Parameter
Each output channel has its own selectable readback time. This time specifies the maximum
duration of the turn off test for the corresponding channel and therefore also the readback
time for turning off the channel.
The following readback times can be set: 1 ms, 5 ms, 10 ms, 50 ms, 100 ms, 200 ms and
400 ms.
You should set an adequately high readback time if the channel involved switches high
capacitive loads. If the readback time for a controlled capacitive load is set too low, the
output channel is passivated because the discharge of the capacitance does not take place
within the turn off test.
If the readback signals are incorrect, the "short circuit" fault causes passivation of the output
channel after the readback time elapses.
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
Parameters of the PM-E F pm DC24V PROFIsafe
Range
10 to 10000 ms
Passivate the entire
module/Passivate
the channel
Activated/
deactivated
1 to 400 ms
Activated/
deactivated
Activated/
deactivated
1 to 400 ms
Activated/
deactivated
7.2 PM-E F pm DC24V PROFIsafe Power Module
Default
Type of Parameter
Assigned by
Static
STEP 7
150 ms
Static
Passivate the
Static
entire module
Activated
Static
1 ms
Static
Deactivated
Static
Activated
Static
1 ms
Static
Deactivated
Static
Fail-Safe Modules
Effective
Range
Module
Module
Module
Channel
Channel
Channel
Channel
Channel
Channel
7-15