Diagnostics
5.2 Fault Diagnostics
Note
Channel-related diagnostics are always updated to the current diagnostic function in the
diagnostic message frame. Subsequent, older diagnostic functions are not deleted.
Remedy: Evaluate the valid current length of the diagnostic message frame in
the RET_VAL parameter of SFC13.
Possible Fault Types of Fail-Safe Modules
The following table lists the messages of the IM151-1 HIGH FEATURE. If you use the
IM 151-7 F CPU, you will obtain detailed diagnostic information using
STEP 7
in
Table 5-1
F-Module
All F-modules
PM-E F pm DC24V
PM-E F pp DC24V
4/8 F-DI DC24V
4 F-DO DC24V/2A
5-6
.
Channel-Specific Diagnostics: Fault Types of Fail-Safe Modules
Fault
Diagnostic Function in
Number
(Fault Type)
1
Short circuit
H
5
Overtemperature
H
9
Fault
H
10
Parameter assignment error
H
11
Sensor voltage or load voltage is
H
missing
13
Communication error
H
4
Overload
H
6
Line break
H
19
Safety-related shutdown
H
19
Safety-related shutdown
H
19
Safety-related shutdown
H
4
Overload
H
6
Line break
H
19
Safety-related shutdown
H
STEP 7
ET 200S Distributed I/O System - Fail-Safe Modules
Hardware Installation and Operating Manual, 07/2005, A5E00103686-04
STEP 7
using
Hardware Diagnostics
Special Meaning for
F-Modules
Short circuit
Overtemperature
Internal fault
Parameter assignment
error
Missing external auxiliary
supply
Communication error
Overload
Wire break
Switching frequency
exceeded
Switching frequency
exceeded
Discrepancy error
Overload
Wire break
Switching frequency
exceeded