Siemens SIMATIC ET 200S Installation And Operating Manual page 86

Distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Fail-Safe Modules
7.3 PM-E F pp DC24V PROFIsafe power module
Safety-Related Shutdown of Standard DO Modules
Warning
The following ET 200S standard modules are approved for safety-related shutdown in
accordance with SIL2:
Warning
Safety-related activation of outputs of standard DO modules is not possible; rather, only
safety-related shutdown is possible. You must therefore take the following effects into
account:
In the worst case you must consider all possible faults of the standard DO modules and the
programs controlling them for which the faults cannot be found directly. For example, the
PM-E F pp DC24V PROFIsafe does not detect external short-circuits as per L+ at the
standard DO module outputs.
All errors of the standard DO modules influence the process via final control elements.
The process must be made known to the F-CPU via sensors and a suitable safety program.
The safety program must react in a safety-related and logically suitable fashion to unwanted
or potentially dangerous states in the process via the PM-E F pp DC24V PROFIsafe and fail-
safe output modules.
If you want to avoid the problems described above completely, we recommend that you use
P/M switching fail-safe electronic modules 4 F-DO DC24V/2A PROFIsafe with standard
ET 200S power modules instead of standard DO modules.
Property of the safety-related shutdown of standard DO modules by the PM-E F pp DC24V
PROFIsafe:
With this cost-effective solution, when a fault is discovered in the process or on the
PM-E F pp DC24V PROFIsafe, there is a comprehensive and simultaneous shutdown of all
outputs involved.
Property of individual shutdown of F-modules with fail-safe outputs:
If a fault is discovered, the extent of the shutdown is kept to a minimum. It is also possible to
react to critical process states staggered over time or outputs can be shut down individually
and safety-related. This solution is expensive compared with the safety-related shutdown by
the PM-E F pp DC24V PROFIsafe.
7-26
2DO DC24V/0.5A (order number 6ES7 132-4BB01-0AA0 or higher)
2DO DC24V/2A (order number 6ES7 132-4BB31-0AA0 or higher)
2DO DC24V/0.5A HIGH FEATURE (order number 6ES7 132-4BB01-0AB0 or higher)
2DO DC24V/2A HIGH FEATURE (order number 6ES7 132-4BB31-0AB0 or higher)
4DO DC24V/0.5A (order number 6ES7 132-4BD00-0AA0 or higher)
4DO DC24V/2A (order number 6ES7 132-4BD31-0AA0 or higher)