Kohler MPAC 1500 Manual page 78

Hide thumbs Also See for MPAC 1500:
Table of Contents

Advertisement

Set Sources, continued
Source Setup Screens Continued from Previous Page:
78
Section 5 Setup
Normal Source
Voltage Unbalance
Dropout
B
Y
"
Back
Normal Source
Set Under Frequency
Pickup
B
Y
"
Back
Normal Source
Set Under Frequency
Dropout
B
Y
"
Back
Normal Source
Set Over Frequency
Pickup
B
Y
"
Back
Normal Source
Set Over Frequency
Dropout
B
Y
"
Back
Normal Source
Set Freq Debounce
B
Y
"
Back
Dropout
??%
5--20%
Save Back
Pickup
??? % of Nominal
80--95%
Save Back
Dropout
??? % of Pickup
95--99%
Save Back
Pickup
??? % of Nominal
105--120%
Save Back
Dropout
??? % of Pickup
101--115% Nominal
Save Back
Debounce Time
?.? Seconds
0.1 -- 15.0 Seconds
Save Back
TP-6714
4/10