8.8
Transient Voltage Surge
Suppressor (TVSS)
A transient voltage surge suppressor (TVSS) is
available for the transfer switch. Installed on the Normal
source side, the TVSS protects the system from voltage
surges, preventing damage to household loads. The
TVSS resets automatically. See Figure 8-19 for TVSS
specifications. See Figure 8-20 for the typical TVSS
assembly location inside the ATS enclosure.
Because of space limitations in the smaller enclosures,
the following models can include either an enclosure
heater or a surge suppressor (TVSS), but not both:
Model KCS 30--200 Amps
Model KSS 40--225 Amps
TVSS Specifications
Surge current
Let-through voltage
Figure 8-19
TVSS Specifications
1
1. TVSS assembly
Figure 8-20
TVSS Location, Typical
8.8.1

Diagnostic LEDs

Red and green indicators on each Transient Voltage
Surge Suppression (TVSS) module indicate protection
status
and
TVSS
condition
replacement). See Figure 8-21 and Figure 8-22.
TP-6714
4/10
100 kA per phase
890 V @ 3 kA
1200 V @ 10 kA
GM69824
(good
or
needs
Note: All leads must be connected and power applied
for the LEDs to illuminate.
If the red indicator is on, the TVSS no longer provides
protection.
Replace the TVSS module.
Section 8.8.3 for replacement instructions.
Green
Red
LED
LED
Status
AC power is present and protection
ON
OFF
is provided.
AC power is present but the TVSS
module needs replacement. The
OFF
ON
remote indication changes state.
AC power or ground is missing:
Verify that wire connections are
correct.
OFF
OFF
Make sure that circuit breaker is
engaged.
Check panel for power.
Figure 8-21
TVSS Diagnostic Indication
1
2
1. Surge suppressor
2. TVSS status indicators
3. Circuit breaker
4. Auxiliary contact terminal block
Figure 8-22
TVSS Assembly, Typical
8.8.2

TVSS Remote Status Indicator

A customer-supplied indicator for the optional transient
voltage surge suppressor (TVSS) can be connected to
provide remote indication when the TVSS needs to be
replaced. The contact changes state when the TVSS
module needs replacement.
Connect customer-provided indicators or alarms to the
normally open (NO) or normally closed (NC) auxiliary
See
3
4
GM70493
Section 8 Accessories
113