Parameter
Outputs
Load Control Mode
Loads to Control
High Current Level
Low Current Level
Load Control # Enable/Disable
Add Priority
Remove Priority
Disconnect (Disc) Time Delay
Load Add Source1 or Source2
Load Remove Src1 or Src2
Figure 5-12
Current-Based Load Control Parameters
72
Section 5 Setup
Assign Load Control Out # to each connected load output. Use
the Set Inputs/Outputs menu. See Section 5.12, programmable
Inputs and outputs.
Select Current for current-based load control. See Section
5.10.2 for more information.
Enter the number of loads to be controlled. Each load must be
connected to a separate output on the main logic board or
accessory I/O module.
If the current rises above this limit, loads will be removed in
order of their remove priority settings until the current falls back
to an acceptable level.
If the current drops below this level and some loads are not
connected, loads will be added in the order of their add priority
setting.
Enable or disable current-based load control for each load on
each source.
Assign a priority for the addition of each load when the current
level falls below the low current level. Add Priority #1 loads are
added first. The add priority and remove priority for a given load
can be different.
Assign a priority for the removal of loads when the current level
rises above the high current level. Remove priority #1 loads are
removed first. The add priority and remove priority for a given
load can be different.
Time delay after a transfer signal to allow disconnection of
selected loads before transfer to the other source. (Operates
when both sources are present.)
Time delay after the current falls below the low limit until the load
is added. Prevents load add caused by a momentary drop in
the current.
Time delay after the current rises above the high limit until the
load is removed. Prevents load removal caused by a
momentary rise in the current.
Description
Adjustment Range
Load Control Out 1--9
None/Time/Current
1--9
0--4000 Amps
0--4000 Amps
Enable or Disable
1--9
1--9
00:00 to 59:59
min:sec
00:00 to 59:59
min:sec
00:00 to 59:59
min:sec
TP-6714
4/10