Set Sources, continued
Source Setup Screens Continued from Previous Page:
Note: The same menus are available
for the Emergency source.
TP-6714
4/10
Set Normal Source
Emergency
B
Y
"
Back
Normal Source
Set Number of Phases
B
Y
"
Back
Normal Source
Set Voltage
B
Y
"
Back
Normal Source
Set Frequency
B
Y
"
Back
Normal Source
Set Under Voltage
Pickup
B
Y
"
Back
Normal Source
Set Under Voltage
Dropout
B
Y
"
Back
Normal Source
Set Over Voltage
Pickup
B
Y
"
Back
Normal Source
Set Over Voltage
Dropout
B
Y
"
Back
Normal Source
Set Voltage Debounce
B
Y
"
Back
Normal Source
Voltage Unbalance
Enable/Disable
B
Y
"
Back
Normal Source
Voltage Unbalance
Pickup
B
Y
"
Back
? Phase
Save Back
Set Voltage
??? VAC
Back
Save
Set Frequency
?? Hz
Back
Save
Pickup
??? % of Nominal
85--100%
Save Back
Dropout
??? % of Pickup
75--98%
Save Back
Pickup
??? % of Dropout
95--100%
Save Back
Dropout
??? % of Nominal
106--135%
Save Back
Debounce Time
?.? Seconds
0.1 -- 9.9 Seconds
Save Back
Voltage Unbalance
Enable/Disable
Save Back
Pickup
??%
3--18%
Save Back
Section 5 Setup