Reset Data; Reset Maintenance Records; Reset Event History; Reset Default Parameters - Kohler MPAC 1500 Manual

Hide thumbs Also See for MPAC 1500:
Table of Contents

Advertisement

3.15 Reset Data

Be sure to read and understand the information in this
section before resetting records or parameters.
Note: Resetting to the default parameters will reset all
parameters to a factory default setting.
Use the Reset Data menus to set records or parameters
back to factory default settings. See Figure 3-25.
1. Use the black arrow buttons to step to the desired
screen.
2. Press the open up arrow button to toggle Yes or No
until Yes is displayed.
3. Press Save to reset the records or parameters to
the factory defaults.
screen without resetting.

3.15.1 Reset Maintenance Records

Reset the maintenance records after transfer switch
service to update the last maintenance date and totals
since reset that are displayed in the maintenance
records screen.
42
Section 3 Operation
Pressing Back exits the

3.15.2 Reset Event History

Resetting the event history clears the events from the
event history log. The history lists the 100 most recent
transfer switch events, including transfers and DIP
switch setting changes as well as faults and alarms.
Note: The event history can be saved to a file before
reset. See Section 3.15.5, File Maintenance.

3.15.3 Reset Default Parameters

Resetting to the default parameters will reset all
parameters, including the system voltage and
frequency, to a factory default setting. The default
system voltage and frequency settings may not match
the settings for your application.
The transfer switch will not operate correctly if the
system voltage and frequency do not match the
sources. Use the Set Sources screen to set the system
voltage and frequency after resetting to the default
parameters. See Section 6 for instructions.
Check the system operation to verify the settings after
resetting.
TP-6714
4/10