Technical Specifications - Johnson Controls T60xDFH-4 Installation Instructions Manual

Low v t-stat, stages heat 1, stages cool 1
Table of Contents

Advertisement

Table 5: Accessories (Order Separately)
Code Number
Description
SEN-600-1
Remote Inside Air Temperature Sensor
Duct Mount Air Temperature Sensor
1
TE-6361M-1
1
Strap-Mount Temperature Sensor
TE-636S-1
2
Cover with Occupancy Sensor
TEC-6H-PIR
1.
Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
2.
The TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR T60xDFH-4 Series Thermostat
Controller to provide occupancy sensing capability.
Table 6: Display Messages
Display
Function
Service
Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2).
Filter
Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2).
Window
Indicates that an outside window or door is open and has cancelled the thermostat controller heating
or cooling action in accordance with the programmable Binary Input (BI1).

Technical Specifications

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and
Occupancy Sensing Capability (Part 1 of 2)
Power Requirements
Relay/Triac
On/Off and
Contact
Floating
Rating
Control
Analog
Proportional
Output Rating
Control
Fan Relay Output Rating
Auxiliary
Triac Output
Output Rating
Digital Inputs
Analog Inputs
Temperature Sensor Type
Wire Size
Temperature
Backlit Display
Range
Heating Control
Cooling
Control
Accuracy
Temperature
Humidity
Minimum Deadband
Ambient
Operating
Conditions
Storage
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A Inrush, Class 2 or SELV
0 to 10 VDC into 2k ohm Resistance (Minimum)
19 to 30 VAC, 1.0 A Maximum, 3.0 A Inrush
19 to 30 VAC, 1.0 A Maximum, 3.0 A Inrush
Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3
Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Coefficient (NTC) Thermistor Sensors
Local 10k ohm Johnson Controls Type II NTC Thermistor Sensor
18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
2F°/1C° between Heating and Cooling
32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing