Table 4: Installer Configuration Menu (Part 6 of 7)
Parameter
Description and Default
Appearing
on Display
TOccTime
Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
an override function enabled
from a remote override (when
the thermostat controller is in the
Unoccupied mode)
a temporary heating or cooling
setpoint
Default: 2.0 hrs
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
Cal RH
Sets the desired humidity sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room humidity
(T603 and T605 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 0.0% RH
Aux cont
Determines the auxiliary contact
function and configuration.
Default: 0
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
Selection Options
Range: 0.0 to 24.0 hrs adjustable in 1-hour increments
Range: 2.0F°/1.0C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -15.0% RH to 15.0% RH adjustable in 1% RH increments
(0)
Not used,
If the sequence of operation is set to
or used for
reheat (2, 3, or 5), ignore this parameter.
reheat
(1)
Auxiliary
Occupied = contact
N.O.
closed
Unoccupied = contact
open
(2)
Auxiliary
Occupied = contact open
N.C.
Unoccupied = contact
closed
(3)
Auxiliary
Occupied and fan On =
N.O.
contact closed
Unoccupied and fan On
or Off = contact open
(4)
Auxiliary
Occupied and fan On =
N.C.
contact open
Unoccupied and fan On
or Off = contact closed
Note: The contact toggles with the Occupied/Unoccupied schedule
of the NSB contact on BI1, if used.
The output
aligns with
occupancy.
The output
aligns with
occupancy
and the
fan on
command.