Technical Specifications - Johnson Controls TEC2104-1 Manual

Networked multi-stage economizer thermostat
Hide thumbs Also See for TEC2104-1:

Advertisement

Technical Specifications

Product
Power Requirements
Relay Contact Rating
Maximum Inductive
Digital Inputs
Economizer Output
Recommended Wire Size
Thermostat Measurement
Range
Sensor Type:
Resolution:
Control Accuracy:
Auxiliary/Outdoor Air
Temperature Indication
Range
Control Range
Minimum Deadband
Ambient Operating
Conditions
Ambient Storage
Conditions
Dimensions (H x W x D)
Shipping Weight
UL and cUL Listing
CE Compliance
FCC Compliance
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
This device complies with Class A Part 15 of the FCC rules. It was also verified to Class B. Operation is subject to
the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received, including interference that may cause undesired operation.
This Class A digital apparatus meets all of the requirements of the Canadian Interference-Causing Equipment
Regulations. Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le materiél
brouilleur du Canada.
Controls Group
507 E. Michigan Street
P.O. Box 423
Milwaukee, WI 53201
TEC2104-1 Thermostat with N2 Bus, Multi-Stage with Economizer Control
20-30 VAC, 50/60 Hz, 24 VAC nominal, 2 VA (RC and C) Class 2
1 ampere with in-rush surges up to 3 amperes, 30 VAC maximum, Class 2
Relay dry contact only across the C terminal to DI1 or DI2
0 to 10 VDC into 2 K ohm resistance minimum
18 gauge maximum, 22 gauge recommended
-40 to 122°F (-40 to 50°C)
Local 10 K ohm NTC thermistor
± 0.2F° (± 0.1C°)
± 0.9F° (± 0.5C°) @ 70°F (21°C) typical calibrated
-40 to 122°F (-40 to 50°C)
Cooling: 54 to 100°F (12 to 37.5°C) in 1/2 degree increments
Heating: 40 to 90°F (4.5 to 32°C) in 1/2 degree increments
(Between heating and cooling) 2F° or 1C°
32 to 122°F (0 to 50°C); 0 to 95% RH noncondensing
-22 to 122°F (-30 to 50°C); 0% to 95% RH noncondensing
4.92 in. x 3.36 in. x 1.13 in. (125 x 86 x 29 mm)
0.75 lb (0.34 kg)
File E27734 with CCN's XAPX (US, UL 873) and XAPX7 (Canada, CSA C22.2 No. 24)
CE Directives EN50081-1: 1992 EMC Emission; EN50082-2 EMC Immunity (Pending)
This equipment has been tested and found to comply with the limits for a Class A digital
device and verified to Class B pursuant to Part 15 of FCC Rules. These limits are designed
to provide reasonable protection against harmful interference when this equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications.
TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions
Published in U.S.A.
www.johnsoncontrols.com
19