Technical Specifications - Johnson Controls TEC3000 Series Installation Manual

On/off or floating fan coil thermostats
Hide thumbs Also See for TEC3000 Series:
Table of Contents

Advertisement

Technical specifications

Table 17: TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual
Zone Thermostat Controllers with Dehumidification Capability
Specification
Power requirements
USB port power rating
Relay contact
On/off or
rating
floating
control
Fan relay output rating
Auxiliary output rating/triac
output
Binary inputs
Analog inputs
Temperature sensor type
Wire size
MS/TP network guidelines
Wireless band (for wireless
models)
Transmission power (for
wireless models)
Transmission range (for
wireless models)
Temperature
Backlit display
range
Heating
control
Cooling control 54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy
Temperature
Humidity
Minimum deadband
Occupancy sensor motion
detection (occupancy sensing
models)
Description
19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or safety
extra-low voltage (SELV)
120 to 250 mA current draw supported
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush,
Class 2 or SELV
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Dry contact across terminal COM to terminals BI1, BI2, or COS
Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm
NTC Type 3 across terminal COM to terminals R SEN or COS
Local digital sensor
18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm
diameter) recommended
For wired models: Up to 100 devices maximum for each Network
Automation Engine (NAE); 4,000 ft (1,219 m) maximum cable
length. Refer to the MS/TP Technical Bulletin for the Metasys, FX, or
Verasys
system installed.
®
For wireless models: Up to 100 devices maximum for each
Network Automation Engine (NAE)
Direct-sequence spread-spectrum 2.4 GHz ISM bands
10 mW maximum
50 ft (15.2 m) recommended indoor
250 ft (76.2 m) line of sight, maximum
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
40.0°F/4.5°C to 90.0°F/32.0°C
±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
±5% RH from 20 to 80% RH at 50°F to 90°F (10°C to 32°C)
2F°/1C° between heating and cooling
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
TEC3000 Series On/Off or Floating Fan Coil Thermostats Installation Guide
61