Johnson Controls T60xDFH-4 Installation Instructions Manual page 4

Low v t-stat, stages heat 1, stages cool 1
Table of Contents

Advertisement

Table 1: Terminal Identification (See Figure 5.)
Terminal
Number
T601DFH-4,
T601DFH-4+PIR
(On/Off Control)
1
Fan-H
2
Fan-M
3
Fan-L
4
24 V~ Hot
5
24 V~ Com
6
BO5 Aux
7
BO5 Aux
8
BO3
9
Blank
10
Blank
11
BO2
12
BI1
13
RS
14
Scom
15
BI2
16
UI3
4
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
Terminal Label
T602DFH-4,
T604DFH-4,
T602DFH-4+PIR,
T604DFH-4+PIR,
T603DFH-4,
T605DFH-4,
T603DFH-4+PIR
T605DFH-4+PIR
(On/Off or
(Proportional 0 to
Floating Control)
10 VDC Control)
Fan-H
Fan-H
Fan-M
Fan-M
Fan-L
Fan-L
24 V~ Hot
24 V~ Hot
24 V~ Com
24 V~ Com
BO5 Aux
BO5 Aux
BO5 Aux
BO5 Aux
BO3
Blank
BO4
AO2
BO1
AO1
BO2
Blank
BI1
BI1
RS
RS
Scom
Scom
BI2
BI2
UI3
UI3
Function
Fan On – High
Fan On – Medium
Fan On – Low
24 VAC from Transformer
24 VAC (Common) from Transformer
Aux BO (Auxiliary Output)
Aux BO (Auxiliary Output)
Open Heat
Close Heat
Open Cool
Close Cool
Configurable Binary Input 1
Remote Room Temperature Sensor
Sensor Common
Configurable Binary Input 2
Configurable Universal Input 3