Table 4: Installer Configuration Menu (Part 7 of 7)
Parameter
Description and Default
Appearing
on Display
Auto Fan
Affects the auto mode of operation
for the following Fan Menu
parameter selection options only:
(2): Low-Med-High-Auto
(3): Low-High-Auto
Default: AS
FL time
Sets the maximum actuator stroke
timing (floating CntrlTyp T602 and
T603 models).
Default: 1.5 min
Cph
Sets the maximum number of cycles
per hour (T601 and on/off CntrlTyp
T602 and T603 models).
Default: 4.0
RA/DA
Choice of reverse or direct acting
analog output signal (T604 and
T605 models)
Default: DA
Reheat
Sets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 dis
Displays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default: -40°F/-40°C
1.
When adjusting the numeric value, press the UP/DOWN arrow key to change the value by single increments; press and
hold the UP/DOWN arrow key to change the numeric value in increments of ten.
Accessories
All the accessories in Table 5 include mounting
hardware; contact the nearest Johnson Controls®
representative to order any of these parts.
Note: Review the technical specifications of the
accessories prior to their use in an application.
20
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
Selection Options
(AS AD): The fan is on Auto during occupied periods. The Med and
High speeds operate automatically on a temperature error from the
setpoint. The Low speed operates Auto on demand. When there is
no demand, the Low speed shuts down. The Low speed is only re-
activated when there is a heating or cooling demand.
(AS): The fan is always on during occupied periods. The fan is on
Auto during unoccupied periods. The Low, Med, and High speeds
operate automatically on a temperature error from the setpoint.
Range: 0.5 to 9.0 min adjustable in 0.5-minute increments
Range: 3.0 to 8.0 cycles per hour
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC
(DA): Direct acting, 0 to 100% = 0 to 10 VDC
(1): 10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric
heat.
(0): 15 minutes (four cycles per hour), for various equipment with
mechanical relays or contactors controlling mechanical reheat
systems.
Used as a diagnostic/service help, to troubleshoot and diagnose
sensor operation.

Repair Information

If the T60xDFH-4 or T60xDFH-4+PIR Series
Thermostat Controller fails to operate within its
specifications, replace the unit. For a replacement
thermostat controller, contact the nearest
Johnson Controls representative.