T600MSP-2 Programmable Thermostat
Application
The T600MSP-2 is a multi-stage programmable
thermostat that provides exceptional accuracy through
the use of a unique Proportional-Integral (PI) time
proportioning algorithm. The algorithm virtually
eliminates temperature offset associated with
traditional, differential-based on/off thermostats. The
T600MSP-2 thermostat also uses an adaptive control
logic algorithm to control the space temperature during
recovery to minimize overshoot while providing
maximum comfort. Additionally, the menu driven
backlit display, plain text menus, and five keys on the
T600MSP-2 thermostat make operating the thermostat
easy and intuitive.
Installation
Location Considerations
Locate the T600MSP-2 thermostat:
on a partitioning interior wall, and approximately
5 ft. (1.5 m) above the floor in a location of
average temperature
away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
away from steam or water pipes, warm air stacks,
unheated/uncooled areas, or sources of electrical
interference
© 2005 Johnson Controls, Inc.
Part No. 24-9889-142, Rev. A
Installation Instructions
Issue Date January 19, 2005
To install the thermostat:
1. Remove the security screw on the bottom of the
thermostat cover using a Phillips-head
screwdriver. Open the thermostat by pulling on the
bottom side of the thermostat cover (Figure 1).
2. Unlock the Printed Circuit Board (PCB) by
carefully pressing the locking tab to the right
(Figure 2). Open the thermostat's PCB to the left.
3. Pull out approximately 6 in. (152 mm) of wires
from the wall and insert the cable through the hole
in the base.
4. Align the base on the wall, and using the base as
a template, mark the location of the two mounting
holes on the wall. Confirm the thermostat base is
installed with the proper side up.
5. Use the supplied anchors and screws for mounting
on drywall or plaster. Drill two 3/16 in. (4.7 mm)
holes at the marked locations and tap nylon
anchors flush to wall surface (Figure 3).
6. Position base on the wall, insert screws through
mounting base, and fasten into wall anchors. Do
not overtighten screws.
7. Swing the thermostat PCB back to the right to
close. Gently press on the PCB to secure each of
the locking tabs.
8. Pull out the screw terminal blocks using the
pull-tabs on each connector (Figure 4).
Note: The number of terminals on the terminal
blocks varies depending on the T600 model.
IMPORTANT:
Use this T600MSP-2
programmable thermostat only as an operating
control. Where failure or malfunction of the
thermostat could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the system. Incorporate and maintain other
devices such as supervisory or alarm systems or
safety or limit controls intended to warn of, or protect
against, failure or malfunction of the thermostat.
1
www.johnsoncontrols.com

Advertisement

loading

Summary of Contents for Johnson Controls T600MSP-2

  • Page 1 2. Unlock the Printed Circuit Board (PCB) by traditional, differential-based on/off thermostats. The carefully pressing the locking tab to the right T600MSP-2 thermostat also uses an adaptive control (Figure 2). Open the thermostat’s PCB to the left. logic algorithm to control the space temperature during 3.
  • Page 2 CAUTION: Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to Figure 3: Mounting the Thermostat Base the equipment. T600MSP-2 Programmable Thermostat Installation Instructions...
  • Page 3 Remote Remote Room Outdoor If using the same power source 24 VAC Sensor Sensor for the thermostat and heating Thermostat Power loads, install a jumper across RC and RH. Figure 5: T600MSP-2 Thermostat Wiring Schematic T600MSP-2 Programmable Thermostat Installation Instructions...
  • Page 4: Setup And Adjustments

    Five keys on the T600 make operation easy and intuitive. Figure 6: T600MSP-2 Thermostat Front Cover Thermostat Interface Keys The T600MSP-2 thermostat interface consists of five keys on the front cover and one configuration key (Figure 7) that is accessed by removing the front cover.
  • Page 5 See the Setting the Minimum Cooling Setpoint (Cool min) section. Configuring the T600MSP-2 Thermostat Sets the Anti-Short Cycle Timer The T600MSP-2 thermostat ships from the factory with Anticycl Default: Two Minutes (2.0 min) default settings for all configurable parameters. The...
  • Page 6 Default: Off set? Y/N See the Enable/Disable Progressive The display now shows the keypad lockout setup Recovery (Prog rec) section. prompt. See the Enabling Keypad Lockout (Lockout) section for instructions. T600MSP-2 Programmable Thermostat Installation Instructions...
  • Page 7 Enabling Keypad Lockout (Lockout) The display now shows the frost protection setup prompt. See the Enabling Frost Protection (Frost pr) The T600MSP-2 thermostat has three levels of keypad section for setup instructions. lockout. The levels and degree of lockout are shown in Table 2.
  • Page 8 CAUTION: Risk of Property Damage. equipment. Do not set the T600MSP-2 thermostat anti-short To set the maximum number of cooling cycles per cycling timer to 0 minutes if the controlled equipment hour while in the Installer Configuration Menu: is not protected by its own internal anti-short cycling timer.
  • Page 9 (the override function can be enabled from the Main User Menu or from one of the digital inputs) or a temporary setpoint is entered. The range is adjustable from 0 to 12 hours. T600MSP-2 Programmable Thermostat Installation Instructions...
  • Page 10 Press YES to store the value. contact can be configured as normally open or normally closed and toggles with the internal occupied/unoccupied schedule (or the remote NSB contact on one of the digital inputs, if used). T600MSP-2 Programmable Thermostat Installation Instructions...
  • Page 11: Operation

    2. Use the UP/DOWN arrow keys to select Normally Display Menu. Open (N.O.) or Normally Closed (N.C.). Press Follow the steps in Table 4 to program the T600MSP-2 YES to store the selection. thermostat. The display now shows the progressive recovery Table 4: Programming the T600MSP-2 Thermostat prompt.
  • Page 12 Note: If the T600MSP-2 thermostat is not in one of these modes, this prompt does not appear. Answering Table 4: Programming the T600MSP-2 YES to this prompt enables the T600MSP-2 Thermostat (Cont.) thermostat to resume the regular scheduled program and setpoints.
  • Page 13 Setpoint. Selecting the System Mode Press YES to change the unoccupied Unocc CL cooling setpoint. Press NO to The T600MSP-2 thermostat has four system modes. set? Y/N advance to the unoccupied heating • Automatic Mode (auto) setpoint.
  • Page 14 Selecting the Fan Mode The T600MSP-2 thermostat has three fan mode Table 6: Programming the Daily Schedule – settings: Two-Event • On Fan Mode (on) Energizes the fan all the time for both occupied Press MENU from the Status RoomTemp...
  • Page 15 Y/N Tuesday. Press YES to set the occupied start time for Monday or NO to advance Occupied to Tuesday (selecting NO leaves the day? Y/N thermostat in the unoccupied mode for the entire day). T600MSP-2 Programmable Thermostat Installation Instructions...
  • Page 16 Upon initial power-up (or after a power loss of greater alarm/backlight should be present). If the day and time than 6 hours), the T600MSP-2 thermostat shows a is incorrect, repeat the Setting the Day and Time SetClock alarm. As the thermostat scrolls through the procedure.
  • Page 17 Accessories Main User Menu: Using the information in Table 9, contact the nearest Johnson Controls® branch office or wholesale 1. Answer NO to all prompts until the schedule hold distributor to order these accessories. prompt appears in the display. Press YES to set the schedule hold type.
  • Page 18: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.