T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers
with Dehumidification and Occupancy Sensing Capability
Installation Instructions
T601DFH-4, T602DFH-4, T603DFH-4, T604DFH-4, T605DFH-4,
T601DFH-4+PIR, T602DFH-4+PIR, T603DFH-4+PIR, T604DFH-4+PIR, T605DFH-4+PIR
Applications
The T60xDFH-4 and T60xDFH-4+PIR Series
Thermostat Controllers provide control of two- or
four-pipe fan coils, cabinet unit heaters, or other
equipment. These thermostat controllers provide
on/off, floating, or proportional 0 to 10 VDC control
outputs; three speeds of fan control; and
dehumidification capability. The T60xDFH-4+PIR
Series Thermostat Controllers have occupancy
sensing capability built into the device. These are
stand-alone devices that maximize up to 30% energy
savings in high-energy usage light commercial
buildings, such as schools and hotels, during occupied
times by using additional Stand-By setpoints. See the
Occupancy Sensor Operation – T60xDFH-4+PIR
Thermostat Controllers section for more information.
The non-programmable T60x Series Thermostat
Controllers provide the user access to parameters such
as system mode, fan mode, and temperature setpoints.
Additionally, the T60x Series has over 20 configurable
parameters enabling the thermostat controllers to
adapt to a variety of applications.
All T60x Series Thermostat Controllers use an intuitive,
plain text, menu-driven backlit display that makes
setup and operation quick and easy. The T60x Series
also employ a unique, Proportional-Integral (PI)
time-proportioning algorithm that virtually eliminates
temperature offset associated with traditional,
differential-based thermostat controllers.
IMPORTANT: The T60xDFH-4 and
T60xDFH-4+PIR Series Thermostat Controllers are
intended to provide an input to equipment under
normal operating conditions. Where failure or
malfunction of the thermostat controller could lead to
personal injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the thermostat controller.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification
Refer to the
QuickLIT Web site
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Location Considerations
Locate the T60x Series Thermostat Controller:
on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature
away from direct sunlight, radiant heat, outside
walls, outside doors, air discharge grills, or
stairwells; and from behind doors
away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
For integrated Passive Infrared (PIR) models, be sure
that the thermostat controller is located centrally, where
occupant movement is abundant.
and Occupancy Sensing Capability Installation Instructions
Part No. 24-9890-951, Rev. A
Issued August 17, 2011
Supersedes October 15, 2009
for the most up-to-date version of this document.
1

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls T60xDFH-4

  • Page 1 For integrated Passive Infrared (PIR) models, be sure that the thermostat controller is located centrally, where occupant movement is abundant. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 2 8. Swing the PCB back to the right and carefully snap the two mounting hole locations. it into the locking tabs on the thermostat controller mounting base. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 3 The security screw comes packaged separately in a plastic bag with the thermostat controller. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 4 Open Cool Blank Close Cool Configurable Binary Input 1 Remote Room Temperature Sensor Scom Scom Scom Sensor Common Configurable Binary Input 2 Configurable Universal Input 3 T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 5 Closed Contact Supply Sensor = Hot Water Changeover Sensor 24 VAC Thermostat Controller Power Figure 5: Wiring the T60xDFH-4 or T60xDFH-4+PIR Series Thermostat Controller (See Table 1.) T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 6 24 V~ 24 V~ 24 V~ Cooling Valve Heating Heating/Cooling Valve Valve Four-Pipe Applications Two-Pipe Applications Figure 9: Wiring T604DFH-4 and T605DFH-4 Thermostat Controllers for Proportional Control T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 7: Setup And Adjustments

    Setup and Adjustments Thermostat Controller Operation Overview Figure 10: Front Cover of Thermostat Controller (T60xDFH-4+PIR Model Shown) Thermostat Controller User Interface Keys • Use the UP/DOWN arrow keys to change the configuration parameters and to activate a setpoint The T60x Series Thermostat Controller user interface adjustment.
  • Page 8: Status Display Menu

    The diagnostic LEDs inside the PIR lens brighten when operation. movement is detected within the first 30 minutes after powerup. The LEDs do not light up or brighten after the initial 30-minute period. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 9 Unoccupied mode when the Unoccupied timer is set above its factory default value of 0.0 hours. Figure 12: Unoccupied Timer Set to 6 Hours and Stand-By Timer Set to 2 Hours T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 10: Configuring Inputs Bi1, Bi2, And Ui3

    Heating Only. See Figure 14 through Figure 19 for 3. When the desired parameter is displayed, use the sequence of operation examples. UP/DOWN arrow keys to choose the desired selection option. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 11 8: Open Heating 9: Proportional Heating 9: N.C. Heating 9: Closed Heating 10: Proportional Cooling 10: N.O. Cooling 10: Open Cooling 11: N.C. Cooling 11: Closed Cooling T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 12 Figure 18: Heating/Cooling, On/Off, Floating, Reheat or Proportional Four-Pipe Applications Device Outputs Closed Temperature Increase (Increments of 1F°/0.5C°) Figure 16: Cooling with Reheat, Two- or Four-Pipe Applications T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 13: Configuring Automatic Fan Speed

    AS AD 100% 2.0F°/1.0C° to 5.0F°/2.5C° Deadband Heating Cooling Valve Valve Temperature Deviation from Setpoint, °F Figure 20: Low-Med-High-Auto and Low-High-Auto Fan Operation T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 14 * These settings disable any local override function. For PIR models, see the Occupancy Sensor Operation – T60xDFH-4+PIR Thermostat Controllers section. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 15 Displays the current humidity (on): Displays the current humidity reading in % RH. reading (T603 and T605 models). (off): Does not display the current humidity reading. Default: off T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 16 (L-H). The default is High. (4): On-Auto: One-speed configuration, (H) Auto is for Fan on demand and On is for Fan on all the time. The default is Auto. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 17 Stand-By and Occupied value can be recovered in a Default: 78.0°F/25.5°C timely fashion when movement is detected in the zone. Range: 54.0°F/12.0°C to 100.0°F/37.5°C T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 18 If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 19 Unoccupied and fan On or Off = contact closed Note: The contact toggles with the Occupied/Unoccupied schedule of the NSB contact on BI1, if used. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 20: Repair Information

    For a replacement thermostat controller, contact the nearest Note: Review the technical specifications of the Johnson Controls representative. accessories prior to their use in an application. T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions...
  • Page 21: Technical Specifications

    Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details. The TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR T60xDFH-4 Series Thermostat Controller to provide occupancy sensing capability.
  • Page 22 The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.