Low v t-stat, stages heat 1, stages cool 1
Table of Contents

Advertisement

Table 4: Installer Configuration Menu (Part 1 of 7)
Parameter
Description and Default
Appearing
on Display
Pswrd
Sets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu.
BI1
Configuration of Binary Input 1.
Default: None
14
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
Selection Options
Range: 0 to 1,000
(None): No function is associated with an input.
(Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When the contact closes, the
thermostat controller goes into the Occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the Occupied mode if the contact is open, until the
TOccTime expires. Advanced PIR occupancy functions using a
Normally Open (N.O.) or Normally Closed (N.C.) remote PIR motion
sensor.
(MotionNC*): Temporary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat controller goes into the Occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the Occupied mode if the contact is closed, until the
TOccTime expires. Advanced PIR occupancy functions using a
Normally Open (N.O.) or Normally Closed (N.C.) remote PIR motion
sensor.
(Window): Cancels the thermostat controller heating or cooling
action when a window is open. The fan operation is only affected if
the Fan Menu parameter is set to (4): On-Auto, and Auto is the
selected fan mode. A Window alarm is displayed indicating that the
window needs to be closed to resume heating or cooling. The
heating and/or cooling outputs are enabled only when the contact is
closed.
* These settings disable any local override function. For PIR
models, see the Occupancy Sensor Operation – T60xDFH-4+PIR
Thermostat Controllers section.