Johnson Controls T60xDFH-4 Installation Instructions Manual page 18

Low v t-stat, stages heat 1, stages cool 1
Table of Contents

Advertisement

Table 4: Installer Configuration Menu (Part 5 of 7)
Parameter
Description and Default
Appearing
on Display
Unocc HT
Sets the Unoccupied heating
setpoint value.
Default: 62.0°F/16.5°C
Unocc CL
Sets the Unoccupied cooling
setpoint value.
Default: 80.0°F/26.5°C
Heat max
Sets the Occupied and Unoccupied
maximum heating setpoint values.
Default: 90.0°F/32.0°C
Cool min
Sets the Occupied and Unoccupied
minimum cooling setpoint values.
Default: 54.0°F/12.0°C
Pband
Sets the proportional band used by
the thermostat controller
Proportional-Integral (PI) control
loop.
Default: 3.0F°/1.7C°
Note: The proportional band
default setting of 3.0F°/1.7C°
provides satisfactory thermostat
controller operation in most
instances. A proportional band
setting other than the default is
normally used in installations where
the location of the thermostat
controller is problematic, leading to
unwanted cycling. An example of a
problematic installation is a wall-
mounted thermostat controller
installed between the return and
supply air feeds, that is directly
influenced by the supply air stream.
Set type
Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent
Spt Func
Determines the operation and
usage of the local setpoint interface
by the user.
Default: Dual Stp
18
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
Selection Options
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
(3): 3.0F°/1.7C°
(4): 4.0F°/2.2C°
(5): 5.0F°/2.8C°
(6): 6.0F°/3.3C°
(7): 7.0F°/3.9C°
(8): 8.0F°/4.4C°
(9): 9.0F°/5.0C°
(10): 10.0F°/5.6C°
(temporar): Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat memory.
(Attch Stp): Single Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. Both the heating and
cooling setpoints are changed simultaneously, while respecting the
minimum configured deadband. If one setpoint is desired over the
other, use the MODE key to toggle between the two setpoints.
(Dual Stp): Dual Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. The heating and cooling
setpoints can be separated individually, allowing the minimum
configured deadband to expand. If one setpoint is desired over the
other, use the MODE key to toggle between the two setpoints.
Note: When adjusting the
temperature, press the UP/
DOWN arrow keys to
change the temperature in
0.5F°/0.5C° increments;
press and hold the
UP/DOWN arrow keys
to change the temperature
in 5.0F°/5.0C° increments.

Advertisement

Table of Contents
loading

This manual is also suitable for:

T60xdfh 4 pir series

Table of Contents