Johnson Controls T60xDFH-4 Installation Instructions Manual page 16

Low v t-stat, stages heat 1, stages cool 1
Table of Contents

Advertisement

Table 4: Installer Configuration Menu (Part 3 of 7)
Parameter
Description and Default
Appearing
on Display
Lockout
Selectable Lockout Levels for
limiting end-user keypad interaction.
Default: 0
Pipe No
Selectable number of pipes in the
system.
Default: 4.0 Pipes
CntrlTyp
Defines the control output for the
type of valves used in the
installation (T602 and T603
models).
Default: Floating
SeqOpera
Determines the sequence of
operation.
Default: 1
Fan Menu
Sets the fan mode options.
Default: 4
16
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
Selection Options
Lockout
Level
Mode
Fan
Setting
Setting
(0)
Access
Access
(1)
Access
Access
(2)
No Access
No Access
(3)
No Access
No Access
(4)
No Access
No Access
(5)
No Access
No Access
(2.0 Pipes): Limits the number of sequences of operation available
from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes): Allows access to all sequences of operation from 0 to 5,
and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating): For three-wire control of 24 VAC floating valves.
Sequence of Operation
(0): Cooling Only (Off-Cool)
(1): Heating Only (Off-Heat)
(2): Cooling and Reheat (Off-Auto*-
Heat-Cool)
(3): Heating and Reheat (Off-Heat)
(4):Cool/Heat Four-Pipe (Off-Auto*-
Heat-Cool)
(5): Cool/Heat Four-Pipe and Reheat
(Off-Auto*-Heat-Cool)
* Auto can be disabled with the AutoMode parameter.
Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between Cooling
Only and Heating Only.
Note: Default parameter settings are always equal to off when the
mode is equal to off.
(0): Low-Med-High: Three-speed configuration using three fan
relays (L-M-H). The default is High.
(1): Low-High: Two-speed configuration using two fan relays (L-H).
The default is High.
(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan
speed mode using three fan relays (L-M-H). The default is High.
(3): Low-High-Auto: Two-speed configuration with Auto Fan speed
mode using two fan relays (L-H). The default is High.
(4): On-Auto: One-speed configuration, (H) Auto is for Fan on
demand and On is for Fan on all the time. The default is Auto.
Function
Local
Occupied
Override
Temperature
Setpoints
Access
Access
No Access
Access
Access
Access
No Access
Access
Access
No Access
No Access
No Access
Default Based on
AutoMode Parameter
Setting
On
Off
Cool
Cool
Heat
Heat
Auto
Heat
Heat
Heat
Auto
Heat
Auto
Heat