Technical specifications

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat
Controllers (Part 1 of 2 )
Power requirements
USB port power rating
Relay contact rating
Binary inputs
Analog inputs
Temperature sensor type
Wire size
MS/TP network guidelines
Wireless band (for wireless
models)
Transmission power (for wireless
models)
Transmission range (for wireless
models)
Temperature
Backlit display
range
Heating control
Cooling control
Accuracy
Temperature
Minimum deadband
Occupancy sensor motion
detection (occupancy sensing
models)
Ambient
Operating
conditions
Storage
TEC3000 Series Networked and Wireless Single- or Two-stage Economizer Thermostat Controllers Quick Start
19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or
safety extra-low voltage (SELV)
120 to 250 mA current draw supported
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
Dry contact across terminal COM to terminals BI1 or BI2
Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across
terminal COM to terminals R SEN
Local digital sensor
18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
For wired models: Up to 100 devices maximum for each Network Automation Engine
(NAE); 4,000 ft (1,219 m) maximum cable length. Refer to the MS/TP Technical
Bulletin for the Metasys, FX, or Verasys® system installed.
For wireless models: Up to 100 devices maximum for each Network Automation
Engine (NAE)
Direct-sequence spread-spectrum 2.4 GHz ISM bands
10 mW maximum
50 ft (15.2 m) recommended indoor
250 ft (76.2 m) line of sight, maximum
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
2F°/1C° between heating and cooling
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
32°F to 122°F (0°C to 50°C); 95% RH maximum, noncondensing
-4°F to 122°F (-20°C to 50°C); 95% RH maximum, noncondensing