Repair Information; Product Warranty - Johnson Controls TEC3000 Series Quick Start Manual

On/off or floating fan coil thermostats
Hide thumbs Also See for TEC3000 Series:
Table of Contents

Advertisement

Table 10: TEC3000 Series Networked and Wireless On/off or Floating Fan Coil and Individual Zone Thermostat
Controllers with Dehumidification Capability technical specifications
Specification
Transmission
ZFR
power (for
ZFR Pro2
wireless
models)
Transmission range (for wireless
models)
Temperature
Backlit display
range
Heating control
Cooling control
Accuracy
Temperature
Humidity
Minimum deadband
Occupancy sensor motion
detection (occupancy sensing
models)
Ambient
Operating
conditions
Storage
Compliance
BACnet
International
United States
Canada
Europe (for
networked
models only)
Australia and New
Zealand
Shipping
Models without
weight
occupancy sensor
Models with
occupancy sensor
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages
resulting from misapplication or misuse of its products.

Repair information

If the TEC3000 Series Thermostat Controller fails to
operate within its specifications, replace the unit. For a
replacement thermostat controller, contact the nearest
Johnson Controls representative.
28
TEC3000 Series On/Off or Floating Fan Coil Thermostats Quick Start Guide
Description
10 mW maximum
100 mW maximum
50 ft (15.2 m) recommended indoor
250 ft (76.2 m) line of sight, maximum
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
±5% RH from 20% to 80% RH at 50°F to 90°F (10°C to 32°C)
2F°/1C° between heating and cooling
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m); based on a clear
line of sight
32°F to 122°F (0°C to 50°C); 95% RH maximum, noncondensing
-4°F to 122°F (-20°C to 50°C); 95% RH maximum, noncondensing
BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Advanced Application
Controller (B-AAC)
UL Listed, File E27734, CCN XAPX, Under UL60730
Networked models: FCC Compliant to CFR 47, Part 15, Subpart B, Class B
Wireless models: Transmission complies with FCC Part 15.247 regulations for low
power unlicensed transmitters; transmitter identification FCC: OEJ-WRZRADIO
ZFR183x: Contains FCC ID: OEJZFRPRO2
UL Listed, File E27734, CCN XAPX7, Under E60730
Networked models: Industry Canada, ICES-003
Wireless models: Industry Canada (IC) RSS-210;
Transmitter identification ZFR1810-1: IC: 279A-WRZRADIO
ZFR183x: Contains IC: 279A-ZFRPRO2
CE Mark – Johnson Controls declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive and the
RoHS Directive.
RCM Mark, Australia/NZ Emissions Compliant
0.75 lb (0.34 kg)
0.77 lb (0.35 kg)

Product warranty

This product is covered by a limited warranty, details
of which can be found at
buildingswarranty.
www.johnsoncontrols.com/