Mitsubishi FX3G Series Programming Manual page 369

Programmable controllers
Hide thumbs Also See for FX3G Series:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
3G
3U
3GC
3UC
Programming Manual - Basic & Applied Instruction Edition
Cautions
1. Input specifications of the input
• An input device X000 to X007 specified as
- High-speed counter
- Input interrupt
- Pulse catch
- Pulse width/Pulse period
- DSZR instruction
- DVIT instruction
- ZRN instruction
• For one input, this instruction can only be used once.
• The maximum frequency of turning the inputs X000 to X007 ON and OFF is shown below:
- FX
/FX
3U
3UC
Used input number
X000 to X005
X006,X007
*1.
When receiving pulses within the response frequency range of 50 k to 100 kHz, perform the following actions:
-
Make sure that the wiring length is 5 m or less.
-
Connect a bleeder resistor of 1.5 kΩ (1 W or more) to the input terminal, and make sure that the load
current in the open collector transistor output of the external equipment is 20 mA or more.
- FX
/FX
3G
3GC
Used input number
X000,X001,X003,X004
X002,X005,X006,X007
2. Occupied devices
1)
When using the 16-bit operation
Three devices are occupied from a device specified in
2)
When using the 32-bit operation
Six devices are occupied from a device specified in
*2.
The value is updated by interrupt processing from the CPU, not every scan time (operation cycle) of the PLC.
3. When a word device is specified as
If the word device value is changed while the instruction is being executed, the change affects the operation in every
measurement cycle.
Function change depending on the version
The function of the FNC 56 instruction varies depending on the PLC version shown in the table below.
Applicable version
FX
FX
3G
Ver. 1.00
Ver. 2.20
or later
or later
Series
S
1
S
PLCs
FX
PLC
3UC
*1
100 kHz
10 kHz
PLCs
Maximum input frequency
FX
/FX
PLCs
3G
3GC
60 kHz
10 kHz
S
2
FX
FX
3U
3GC
3UC
Ver. 1.40
Ver. 2.20
or later
or later
13 High-Speed Processing – FNC 50 to FNC 59
cannot overlap the following functions or instructions:
1
Maximum input frequency
FX
3U
Main unit
*1
100 kHz
10 kHz
*2
D
.
*2
D
.
.
Item
Addition of 32-bit instruction
13.7 FNC 56 – SPD / Speed Detection
PLC
FX
-4HSX-ADP
3U
200 kHz
Outline of function
32-bit operations (DSPD) are enabled.
11
12
13
14
15
16
17
18
19
20
367

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u seriesFx3gc seriesFx3uc series

Table of Contents