3U
3GC
3UC
Programming Manual - Basic & Applied Instruction Edition
11.6.1
Replacement of SFT instruction in F
SFT instruction in F
below:
1. F
and F
PLCs
1
2
M100: Input data
M101 to M117 (octal number): 15-step shift register
Circuit program
X000
data input
shift input
X001
reset input
X002
2. FX
, FX
, FX
3G
3U
data input
X000
shift input
X001
X002
reset input
Series
/F
PLCs corresponds to SFTL (FNC 35) instruction in FX
1
2
OUT
M100
SFT
M117
RST
and FX
PLCs
3GC
3UC
M101 to M115 (decimal number): 15-step shift register
M100
FNC 35
M100
SFTLP
Input data
FNC 40
M101
ZRST
Head
device
11 Rotation and Shift Operation – FNC 30 to FNC 39
and F
Series
1
2
List program
0000
LD
X000
0001
OUT
M100
0002
LD
X001
0003
SFT
M100
0004
LD
X002
0005
RST
M100
Fixed value
M101
K 15
K 1
Head
Number
Shift by
device
of steps
1 bit
Shift registers M101 to M115 are reset
M115
at one time.
11.6 FNC 35 – SFTL / Bit Shift Left
/FX
/FX
/FX
PLCs as shown
3G
3U
3GC
3UC
11
12
13
14
15
16
17
18
19
20
299