7.2
Applied operations by an I/O signal (operation from
the terminal block)
Input terminal sink and source logic are set by using slide switch SW1.
7.2.1
This function is used to send a signal to the
input terminal from an external programmable
controller to operate or configure the inverter.
The ability to select from a variety of functions
allows for flexible system design.
Default settings of slide switch SW1and SW2 are
as follows;
SW1: PLC side, SW2: VIB side and S3 side.
Refer to page B-11 to 13 for details.
7
Settings for the logic input terminal function
Terminal
symbol
F
R
RES
S1
S2
S3
VIB
VIA
VIA
VIB
F to VIB
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Input terminal function
(sink logic)
Title
Function
Input terminal selection 1A (F)
Input terminal selection 1B (F)
Input terminal selection 1C (F)
Input terminal selection 2A (R)
Input terminal selection 2B (R)
Input terminal selection 2C (R)
Input terminal selection 3A (RES)
Input terminal selection 3B (RES)
Input terminal selection 4A (S1)
Input terminal selection 4B (S1)
Input terminal selection 5 (S2)
Logic
input
/ pulse
f146
selection (S2)
Input terminal selection 6 (S3)
Logic input / PTC input selection (S3)
f147
Input terminal selection 7 (VIB)
Input terminal selection 8 (VIA)
Analog/logic input selection (VIA/VIB)
Input terminal response time
[Control terminal block]
SW2
VIB
PTC
VIA
VIB
CC
VIC
PP
CC
NO
OUT
P24
F
Adjustment range
0-203 Note 1)
0-203 Note 1)
0-203 Note 1)
0-203 Note 1)
0-203 Note 3)
train input
0: Logic input
1: Pulse train input
0-203 Note 4)
0: Logic input
1: PTC input
0-203 Note 5)
8-55 Note 6)
0-4
1-1000 (ms) Note 7)
G-2
E6581611
SW1
SOURCE
SINK
S4
S3
PLC
S3
FM
FLA
FLB
FLC
R
CC
+SU
+24
S1
S2
RES
Default setting
2 (F)
0 (No function)
0 (No function)
4 (R)
0 (No function)
0 (No function)
8 (RES)
0 (No function)
10 (SS1)
0 (No function)
12 (SS2)
0
14 (SS3)
0
16 (SS4)
24 (AD2)
0
1
RY
RC