6.7
Terminal function selection
6.7.1
f104 : Always active function selection 1
f108 : Always active function selection 2
f110 : Always active function selection 3
[Parameter setting]
Note1) Input terminal function 8, 9 (Reset command and its inversion) cannot be assigned.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Keeping an input terminal function always active (ON)
Function
This parameter specifies an input terminal function that is always to be kept active (ON).
Title
Function
f104 Always active function selection 1
f108
Always active function selection 2
f110
Always active function selection 3
Explanation of the coast stop function
When ST (Standby) is OFF, coast stops.
The default setting for ST (Standby) is ON. Please
change the following settings:
(no function)
Assign open input terminal 6: ST (Standby).
Coast stops if terminal set for ST (Standby) is set to
OFF. The monitor on the inverter at this time displays
Adjustment range
0-7, 10-153: Refer to section 11.6.
8,9: -
0-7, 10-153: Refer to section 11.6.
8,9: -
0-7, 10-153: Refer to section 11.6.
8,9: -
Motor
speed
F-CC
ST-CC
F-31
E6581611
Default setting
0 (No function)
0 (No function)
6
6 (ST)
Coast stop
ON
OFF
ON
OFF