f405: Set the motor's rated capacity according to the motor's name plate or test report.
f415: Set the rated current of the motor. For the rated current, see the motor's nameplate or test report.
f417: Set the rated rotational speed of the motor. For the rated current, see the motor's nameplate or test
● Adjustment method for the moment of inertia of the load
f459: Adjusts the excess response speed. A larger value gives a smaller overshoot at the
thr : If the rated capacity of the motor is one size smaller than that of the inverter, lower the thermal
Caution:
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
report.
acceleration/deceleration completion point. In the default settings, the moment of inertia of the load
(including the motor shaft) value is optimally set considering a motor shaft of 1x. When the
moment of inertia of the load is not 1x, set a value that matches that actual moment of inertia of
the load.
protective level according to the rated current of the motor.
*Sensorless vector control may not operate properly if the motor capacity differs from the
applicable rated capacity of the inverter by more than two grades.
If a combination of the inverter rating and the motor capacity is different for more than 2 items, PM
motor control may not operate correctly.