Chapter 3 — System and site requirements
All conductors must terminate in a permanent way. Make sure all
terminations are easily visible and available for maintenance purposes.
Tag ground connections with a clear message such as "CRITICAL
CONNECTION: DO NOT REMOVE OR DISCONNECT".
Table 10
Area-specific grounding wire requirements
Area
Germany
Other areas in Europe
UK
For an installed Option 11C Mini, the impedance of the link between
the ground post of the Main Chassis and the single point ground to
which it connects must be less than 0.25 Ohms.
Transients in supply conductors and ground systems can damage
integrated circuits. This damage can result in unreliable Option 11C
Mini operation. Damage caused by transients is not always
immediately apparent. Degradation can occur over a period of time.
Grounding wire requirements
#8 AWG (10 mm
not smaller than #6 AWG (16 mm
point
two green/yellow wires no thinner than two
2
10 mm
CAUTION
CAUTION
Option 11C Mini
Planning and Installation Guide
Page 49 of 332
2
) green/yellow wire
2
) at any