Mk7 Keypad/Keyprox Addressing; Adding A Mk7 Keypad/Keyprox To The System - Honeywell Galaxy 2 Series Installation Manual

Hide thumbs Also See for Galaxy 2 Series:
Table of Contents

Advertisement

Peripherals (cont'd)
4. If you are using a wall-run cable for the keypad (A, B, +, -) position the cable behind the back plate in
the cable channels provided. The cable can be run in from either the top or the bottom of the back plate.
Use a sharp tool to remove the plastic from the top or the bottom of the cable guides on the back plate
skirting.
CAUTION:
Use of any screws other than No. 6 Pan-head can damage the keypad
mouldings.
5. Make sure that the keypad wiring is fed through the large opening on the keypad backplate, then
position the keypad base on the wall and attach it securely with the three No. 6 Pan-head screws.
6. If an off the wall tamper is required, using a No. 6 Pan-head screw, secure the sacrificial wall
tamper, indicated in Figure 18, to the wall. Make sure that the tamper knockout is still
connected to the backplate moulding.
7. Connect the A, B and power wires to the correct terminals of the removable, four-way connector
block.

Mk7 Keypad/Keyprox Addressing

The valid keypad/keyprox addresses are: 0, 1, 2, and 3. A 16-way Rotary Address Switch is used to ad-
dress the Keypad/keyprox. The address switch assigns a hexadecimal address value to the keypad/keyprox.
NOTE: Any change to the keypad address must be made when the power is disconnected from the keypad.

Adding a Mk7 Keypad/Keyprox to the System

When adding a keypad to an existing system, the following points must be considered:
1. Ensure that the keypad to be added has a unique address from the other keypads on the system.
2. Ensure that the keypad has a valid address.
3. Connect the keypad to the system - refer to the Keypad Installation Procedure.
4. Access engineer mode.
5. Connect the RS485 (AB) line of the keypad in parallel with the RS485 (AB) line of the
existing keypads.
6. Connect + and – terminals of the keypad to a power supply.
7. Exit engineer mode - engineer code + esc.
7. The Mk7 keypad displays the message 1 MOD. ADDED — esc=CONTINUE. Press the esc
key; the keypad returns to the unset banner. If this message is not displayed, the keypad is not
communicating with the control panel and has not been configured into the system.
8. The keypad is now configured into the system.
Galaxy 2 Series Installation Manual
26

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents