Wireless Zone Expansion; Figure 7: Keypad Addressing - Honeywell VISTA-128BPT Installation And Setup Manual

Commercial burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-128BPT:
Table of Contents

Advertisement

Addressing the Keypads
The keypads do not operate until they
are physically addressed and enabled
in the system's Device Programming
(in the #93 Menu Mode).
• Set each keypad for an individual address
(00-30) according to the keypad's
instructions.
• Set an alpha keypad for address 00 and
other keypads for higher addresses (00 and
01 are enabled in the system's default
program).
By default, any keypads set for address 02
and above will appear blank until they are
enabled in the system's program.
• Each keypad must be set for a different
address.
Do not set any keypads to address 31 (non-addressable mode). They will interfere with other keypads (as
well as other devices) connected to the keypad terminals.

Wireless Zone Expansion

The 5881ENHC RF Receiver, 5869 Holdup Switch Transmitter and 5817CBXT Wireless Commercial
UL
Household Transmitter are listed for UL Commercial Burglary applications. Not all other RF receivers and
transmitters are listed for UL Commercial Burglary applications.
ULC
Wireless devices are not ULC Listed and cannot be used for ULC Installations.
The following table lists the receivers that may be used and the number of zones they support.
RF System Operation and Supervision
The 5800 RF system operation has the following
characteristics:
• The receiver responds to a frequency of 345MHz.
• The receiver has a nominal range of 200 feet.
• Supervised transmitters send a supervisory
signal every 70-90 minutes.
Zones 988 (2
nd
receiver) and 990 (1
are used to supervise the RF reception of both
receivers. The reception is supervised for two
conditions:1. The receiver goes "deaf" (does not
hear from any transmitter) within a programmed
interval of time (defined by program field 1∗30).
Compatible 5800 Series Receivers
Commercial
Receiver
Zones
5881ENHC
up to 250
5883H
Up to 250
st
receiver)
SECTION 4: INSTALLING THE CONTROL

Figure 7: Keypad Addressing

Residential
Receiver
Zones
5881EN-L
Up to 8
5881EN-M
Up to 16
5881EN-H
Up to 250
2. Proper RF reception is impeded (i.e., jamming or
other RF interference). The control checks for this
condition every 45 seconds.
A response type (05 Day/Night) must be
UL
programmed for zones 990 (1
and 988 (2
nd
installations.
• The 5881ENHC receiver contains front and back
tampers that permit its use in commercial burglary
installations.
• You may only mount the 5881ENHC its own plastic
housing. Otherwise, the receiver constantly reports
a tamper condition.
4-5
st
receiver)
receiver) for UL