Main Functions
1.7

Thermostat Control

Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Thermostat OFF Condition
Thermostat ON Condition
<Cooling / Dry>
<Heating>
Refer to "Temperature Control" on page 10 for detail.
16
The temperature difference is in the zone A.
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
C
–1.5˚C
B
A
OFF
OFF
OFF
A A
B B
1.0˚C
C C
Room thermistor temperature – target temperature
ON
Cooling : –0.5˚C
Dry : –0.5˚C
Cooling : –2.0˚C
Dry : –2.5 ~ –2.0˚C
Room thermistor temperature – target temperature
1.5˚C
0˚C
ON
ON
SiBE041102_A
(R12319)
(R12320)
Function and Control