Thermistor Or Related Abnormality (Indoor Unit) - Daikin FTXN25KEV1B Service Manual

Inverter pair wall mounted type k-series
Hide thumbs Also See for FTXN25KEV1B:
Table of Contents

Advertisement

SiBE041102_A
4.5

Thermistor or Related Abnormality (Indoor Unit)

C4 , C9
Remote
Controller
Display
Method of
The temperatures detected by the thermistors determine thermistor errors.
Malfunction
Detection
Malfunction
The thermistor input is more than 4.96 V or less than 0.04 V during compressor operation.
Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.01
Refer to P.87
C4
C9
Service Diagnosis
Disconnection of connector
Defective thermistor
Defective indoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the connection of
connectors.
Is it normal?
YES
Check No. 01
Check the thermistor resistance
value.
Is it normal?
YES
: Indoor heat exchanger thermistor
: Room temperature thermistor
NO
NO
Troubleshooting
Correct the connection.
Replace the thermistor.
Replace the indoor unit PCB.
(R14406)