Indoor Unit; Removal Of Air Filters - Daikin FTXN25KEV1B Service Manual

Inverter pair wall mounted type k-series
Hide thumbs Also See for FTXN25KEV1B:
Table of Contents

Advertisement

Indoor Unit

1. Indoor Unit

1.1

Removal of Air Filters

Procedure
Step
1. Appearance features
2. Remove the air filters.
1
Open the front panel to
the position where it
stops.
Slightly push up the
2
knob at the center of
the air filter.
96
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Signal receiver
ON/OFF button
(Forced operation ON/OFF button)
Front panel
Air filter
Hook
Room temperature thermistor
(R11616)
Operation
lamp
TIMER
lamp
(R11617)
(R11618)
(R14598)
SiBE041102_A
Points
Warning
Dangerous: High voltage
A high voltage is applied to
all the electric circuits of this
product including
thermistors.
When a signal from the
remote controller is
received, the receiving tone
sounds and the operation
lamp flickers immediately to
confirm the signal reception.
When the ON/OFF button is
kept pressed for 5 seconds,
the forced cooling operation
is performed for about 15
minutes.
The air filter is not marked
for difference between the
right and left sides.
The air filter can be set
easily by inserting it along
the guides.
Insert the air filter with the
"FRONT" mark faced up.
Be sure to insert the hooks
(at 2 lower positions) when
mounting the air filter.
Removal Procedure