Daikin FTX09NMVJU Installation Manual
Hide thumbs Also See for FTX09NMVJU:

Advertisement

Quick Links

MODELS
FTX09NMVJU
FTK09NMVJU
FTX12NMVJU
FTK12NMVJU
FTX18NMVJU
FTK18NMVJU
FTX24NMVJU
FTK24NMVJU
FTXN09NMVJU
FTKN09NMVJU
FTXN12NMVJU
FTKN12NMVJU
FTXN18NMVJU
FTKN18NMVJU
FTXN24NMVJU
FTKN24NMVJU
DAIKIN ROOM AIR CONDITIONER
INSTALLATION MANUAL
R410A Split Series
Installation manual
Manuel dinstallation
Manuel dinstallation
Manual de instalación

Advertisement

Table of Contents
loading

Summary of Contents for Daikin FTX09NMVJU

  • Page 1 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manuel dinstallation Manual de instalación MODELS FTX09NMVJU FTK09NMVJU FTX12NMVJU FTK12NMVJU FTX18NMVJU FTK18NMVJU FTX24NMVJU FTK24NMVJU FTXN09NMVJU FTKN09NMVJU FTXN12NMVJU FTKN12NMVJU FTXN18NMVJU FTKN18NMVJU FTXN24NMVJU FTKN24NMVJU...
  • Page 2: Safety Considerations

    Contents Safety Considerations ������������������������������������ 1 Refrigerant Piping Work ��������������������������������� 9 1. Flaring the pipe end ............. 9 Accessories ����������������������������������������������������� 3 2. Refrigerant piping ............ 9 Choosing an Installation Site ������������������������ 3 Installation Tips ����������������������������������������������� 10 1. Indoor unit .............. 3 1. Removing and installing the front panel ...... 10 2. Wireless remote controller ........... 3 2. Removing and installing the front grille......11 3. How to set the different addresses ......11 Indoor Unit Installation Drawings �����������������...
  • Page 3 • Do not install unit in an area where flammable materials • When installing or relocating the system, be sure to keep are present due to risk of explosion resulting in serious the refrigerant circuit free from all substances other than injury or death. the specified refrigerant (R410A), such as air. (Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise which • Do not ground units to telephone wires or lightning rods may result in rupture, resulting in injury.) because lightning strikes could cause a severe shock hazard resulting in severe injury or death, and to gas • During pump down, stop the compressor before removing pipes because a gas leak could result in an explosion the refrigerant piping. which could lead to severe injury or death. If the compressor is still running and the stop valve is open during pump down, air will be sucked in when the refrigerant piping is removed, causing abnormally high WARNING pressure which could lead to equipment damage or and personal injury. • Installation shall be left to the authorized dealer or another • During installation, attach the refrigerant piping securely trained professional. before running the compressor. Improper installation may cause water leakage, electrical If the refrigerant pipes are not attached and the stop valve shock, fire, or equipment damage. is open during installation, air will be sucked in when the • Install the air conditioner according to the instructions compressor is run, causing abnormally high pressure given in this manual. which could lead to equipment damage and personal Incomplete installation may cause water leakage, injury.
  • Page 4: Choosing An Installation Site

    Accessories Mounting plate fixing screw Titanium apatite photocatalytic Mounting plate 3/16” × 1” (M4 × 25mm) air-purifying filter * Fixing screw for remote controller Wireless remote controller Remote controller holder holder 1/8” × 13/16” (M3 × 20mm) Indoor unit fixing screw G Dry battery AAA. LR03(alkaline) Insulation tape 3/16” × 1/2” (M4 × 12mm) Operation manual Installation manual Only for FTX(K)09/12/18/24* 09/12 class: without frame 18/24 class: with frame Choosing an Installation Site Before choosing the installation site, obtain user approval. 1� Indoor unit The indoor unit should be positioned in a place where: 1) the restrictions on the installation requirements specified in “Indoor unit installation drawings” on page 4 are met, 2) both the air inlet and air outlet are unobstructed, 3) the unit is not exposed to direct sunlight, 4) the unit is away from sources of heat or steam, 5) there is no source of machine oil vapour (this may shorten the indoor unit service life), 6) cool/warm air is circulated throughout the room, 7) the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may affect the remote controller range, 8) the unit is at least 3.3ft (1m) away from any television or radio set (the unit may cause interference with the picture or sound), 9) no laundry equipment is nearby.
  • Page 5: Indoor Unit Installation Drawings

    Indoor Unit Installation Drawings How to attach the indoor unit Mounting Hook the hooks of the bottom frame plate to the mounting plate. A Mounting plate If the hooks are difficult to hook, remove the front grille. Hook How to remove the indoor unit Push up the marked area (at the lower part of the front grille) to Bottom frame...
  • Page 6: Indoor Unit Installation

    Indoor Unit Installation 1� Installing the mounting plate • The mounting plate should be installed on a wall which can support the weight of the indoor unit. 1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the drilling points on the wall. 2) Secure the mounting plate to the wall with screws. Recommended mounting plate retention spots and dimensions 09/12 class Recommended mounting plate Place a leveler retention spots (7 spots in all) on these tabs. Through-the-wall hole φ2-9/16 (65) Drain hose position 4-5/8 (117) 4-5/8 (116.5)
  • Page 7: Drilling A Wall Hole And Installing Wall Embedded Pipe

    2� Drilling a wall hole and installing wall embedded pipe • For metal frame or metal board walls, be sure to use a wall embedded pipe and wall hole cover in the feed-through hole to prevent possible heat, electrical Wall embedded shock, or fi re. pipe Inside Outside (field supply) • Be sure to caulk the gaps around the pipes with caulking material to prevent Caulking (field supply) water leakage. 1) Drill a feed-through hole with a φ2-9/16 inch (65mm) (for 09/12 class), φ3-1/8 inch (80mm) (for 18/24 class) diameter through the wall at a downward angle toward the outside. Wall hole cover (field supply) 2) Insert a wall embedded pipe into the hole. 3) Insert a wall hole cover into wall pipe. 4) After completing refrigerant piping, wiring, and drain piping, caulk the pipe hole gap with putty.
  • Page 8 Indoor Unit Installation 3-2� Left-side, left-back, or left-bottom piping How to replace the drain plug and drain hose • Replacing onto the left side Drain hose attachment position The drain hose is on the back of the unit. 1) Remove the fixing screw of drain hose on the right and remove the drain hose. 2) Remove the drain plug on the left side and attach it to the right side.
  • Page 9: Drain Piping

    4� Wiring 1) As shown in the illustration, insert the wires including the ground wire into the conduit and secure them with lock nut onto the conduit mounting plate. 2) Strip wire ends (3/4 inch (20mm)). 3) Match wire colours with terminal numbers on the terminal block of indoor and outdoor unit and fi rmly secure the wires in the corresponding terminals with screws. 4) Connect the ground wire to the corresponding terminals. 5) Pull the wires lightly to make sure they are securely connected. 6) While close the service lid, shape the wires so that the service lid fi ts securely, then close the service lid. Terminal block Firmly fix the wires with the terminal screws. Outdoor unit Electrical wiring box Use AWG16 if the connection wire Shape wires so that the 1 2 3 length is less than 33ft (10m), or service lid fits securely.
  • Page 10: Refrigerant Piping Work

    Refrigerant Piping Work 1� Flaring the pipe end 1) Cut the pipe end with a pipe cutter. 2) Remove burrs with the cut surface facing downward Cut exactly at right angles. Remove burrs. so that the chips do not enter the pipe. Flaring 3) Put the flare nut on the pipe. Set exactly at the position shown below. 4) Flare the pipe. Flare tool for R410A Conventional flare tool Clutch-type Clutch-type (Rigid-type) Wing-nut type (Imperial-type) 5) Check that the flaring is properly made.
  • Page 11: Installation Tips

    2-2� Selection of copper and heat insulation materials When using commercial copper pipes and fi ttings, observe the following: Inter-unit wire Gas pipe • Insulation material: Polyethylene foam Liquid pipe Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 0.045kcal/mh°C)) Be sure to use insulation that is designed for use with HVAC Systems. Liquid pipe • ACR Copper only. Gas pipe insulation insulation Finishing tape Drain hose • Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as below. Thermal insulation Piping size Minimum bend radius Piping thickness Thermal insulation size...
  • Page 12: Removing And Installing The Front Grille

    2� Removing and installing the front grille • Removal method  mark area 1) Remove the front panel to remove the air fi lter. Upper hook (3 locations) Push Upper hook down. 2) Remove the 2 screws from the front grille. (The 18 and 24-class models have 3 screws.) 3) In front of the mark on the front grille, there are 3 upper hooks. Lightly pull the front grille toward you with one hand, and push down on the hooks with the fi ngers of your other hand. When there is insuffi cient work space because the unit is close to ceiling 1) Push up.
  • Page 13: Trial Operation And Testing

    Trial Operation and Testing 1� Trial operation and testing • Trial operation should be carried out in either COOL or HEAT operation. 1-1� Measure the supply voltage and make sure that it is within the specifi ed range. 1-2� In COOL operation, select the lowest programmable temperature; in HEAT operation, select the highest programmable temperature� 1-3�...
  • Page 14 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manuel dinstallation Manual de instalación MODELS RX09NMVJU RK09NMVJU RX12NMVJU RK12NMVJU RX18NMVJU RK18NMVJU RX24NMVJU RK24NMVJU RXN09NMVJU RKN09NMVJU RKN12NMVJU RXN12NMVJU RXN18NMVJU RKN18NMVJU RXN24NMVJU RKN24NMVJU...
  • Page 15 Contents Safety Considerations ........1 4. Refrigerant piping ............6 5. Pressure test and evacuating system ......7 Accessories ............. 3 6. Refilling refrigerant ............8 7. Refrigerant piping work ..........8 Precautions for Selecting the Location ..3 Wiring ............... 9 Precautions on Installation ......
  • Page 16 pressure which could lead to equipment damage or and WARNING personal injury. • Installation shall be left to the authorized dealer or another • During installation, attach the refrigerant piping securely trained professional. before running the compressor. Improper installation may cause water leakage, electrical If the refrigerant pipes are not attached and the stop valve shock, fire, or equipment damage.
  • Page 17: Precautions For Selecting The Location

    Accessories Accessories supplied with the outdoor unit: Drain socket* Installation manual It is on the bottom packing case. Drain cap (1)* Drain cap (2)* 09/12 class 09/12 class 18/24 class 18/24 class *Only for heat pump models. Precautions for Selecting the Location 1) Choose a place solid enough to bear the weight and vibration of the unit, where the operating sound will not be amplifi ed.
  • Page 18: Precautions On Installation

    Precautions on Installation • Check the strength and level of the installation surface so that the unit does not cause any operating vibration or noise after installation. • In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare 4 sets of M8 or M10 foundation bolts, nuts and washers; all separately available.) • It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm) from the foundation surface. Outdoor Unit Installation Drawings RX09/12∗...
  • Page 19: Outdoor Unit Installation

    Installation Guidelines • Where a wall or other obstacle is in the path of the outdoor unit’s intake or exhaust airflow, follow the installation guidelines below. • For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less. 09/12 class Wall facing one side Walls facing two sides More than More than 1-15/16 (50) 3-15/16 (100) More than 5-7/8 (150) More than 47-1/4 3-15/16 (100) (1200) or less More than More than 1-15/16 (50) 1-15/16 (50) Side view...
  • Page 20: Drain Work

    Drain work 09/12 class 18/24 class Drain cap (1) Drain cap (1) (only for heat pump models) Drain cap (2) Drain cap (2) • If the drain port is covered by a mounting base or floor Drain cap (1) surface, place additional foot bases of at least 1-1/4 Drain inch (30mm) in height under the outdoor unit’s feet. Drain Drain cap (2) socket Air outlet side...
  • Page 21: Pressure Test And Evacuating System

    Outdoor Unit Installation Pressure test and evacuating system WARNING • Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle. • If refrigerant gas leaks should occur, ventilate the room as soon and as much as possible. • R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment. • Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit. • When piping work is complete, it is necessary to perform a pressure test Compound Pressure High-pressure...
  • Page 22: Refilling Refrigerant

    Refilling refrigerant Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. This is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
  • Page 23 Wiring WARNING • Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire. • Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire. • Be sure to install a ground fault circuit interrupter. (One that can handle higher harmonics.) (This unit uses an inverter, which means that a ground fault circuit interrupter capable of handling harmonics must be used in order to prevent any malfunction of the ground fault circuit interrupter itself.) • Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.
  • Page 24 18/24 class <Method of mounting conduit> 1) Dismount the service lid by removing the 2 screws. 2) Pass wires through the conduit and secure them with a lock nut. 3) After completing the work, reattach the service lid to its original position. Power supply Service lid terminal block...
  • Page 25: Facility Setting* (Cooling At Low Outdoor Temperature)

    Facility Setting* (cooling at low outdoor temperature) This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in a residence or offi ce (the space where there is a human). *Only for RX and RK models.
  • Page 26 Trial Operation and Testing Trial operation and testing • Trial operation should be carried out in either COOL or HEAT operation. 1-1. Measure the supply voltage and make sure that it is within the specifi ed range. 1-2. In COOL operation, select the lowest programmable temperature; in HEAT operation, select the highest programmable temperature.

Table of Contents